V8 VRF Indoor Units
59
Troubleshooting Guide
be any integer
from 0 to 62,
denoted by X, and
the adjacent
address is: X+1
40≤kW<78.5
14≤HP<28
1
4
The minimum
address code can
be any integer
from 0 to 60,
denoted by X, and
the adjacent
address is: X+1,
X+2, X+3
Minimum
address code X
78.5≤kW<101
28≤HP<36
1
5
The minimum
address code can
be any integer
from 0 to 59,
denoted by X, and
the adjacent
address is: X+1,
X+2, X+3, X+4
Minimum
address code X
101≤kW<112
36≤HP<40
1
6
The minimum
address code can
be any integer
from 0 to 58,
denoted by X, and
the adjacent
address is: X+1,
X+2, X+3, X+4,
X+5
Minimum
address code X
kW>112
HP>40
1
8
Minimum address
code can be any
integer from 0 to
56, denoted by X,
and the adjacent
address is: X+1,
X+2, X+3, X+4,
X+5, X+6, X+7
Minimum
address code X
Example: If one IDU is 5 HP and the address code is set to 1, then the query address at the centralized
controller side or wired controller side is 1. If one IDU is 20 HP and the address code is set to 5, then this
IDU has four address codes, which are 5, 6, 7, and 8, but the query address at the centralized controller
side or wired controller side is 5.