8.4.5 Dehumidify mode
8.4.5.1 Indoor fan speed is fixed in breeze and can’t be changed. The louver angle is the same as in
cooling mode.
8.4.5.2 Compressor running rules
8.4.5.3 Room over low temperature protection
If room temperature is lower than 10, compressor will stop and not resume until room temperature
over 12.
8.4.5.4 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit
frequency limit are valid, and they are the same as that in cooling mode.
8.4.5.5 The outdoor fan operates same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
Pressing the touch button once, the machine will transfer into forced auto mode, if pressing the button
once again, the machine will turn into forced cooling mode, the third pressing will stop the unit, and the
forth pressing is the start of the cycle of forced auto mode, forced cooling mode and stop. Refer the
following chart:
8.4.6.2 In forced operation mode, all general protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the