EasyManua.ls Logo

Minebea Intec MiNexx-link-E PR 5215/10 - Page 94

Default Icon
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Operating | 6.12 - Configuring the analog output | 94
Parameter table (continued)
Parameter Selection Description
[linear] In the event of a negative weight, the analog
output is retained. This is only possible if the
output value for the zero weight is >0mA.
[0mA] In the event of a negative weight, the analog
output is set to 0mA.
[4mA] In the event of a negative weight, the analog
output is set to 4mA.
[On <0]
[20mA] In the event of a negative weight, the analog
output is set to 20mA.
[linear] In the event of a weight >Max, the analog out
put is retained. This is only possible if the out
put value for Max is <20 mA.
[0mA] In the event of a weight >Max, the output is set
to 0mA.
[4mA] In the event of a weight >Max, the output is set
to 4mA.
[On > Max]
[20mA] In the event of a weight >Max, the output is set
to 20mA.
[Analog value] Input: fixed analog val
ue
Only possible if [Transparent] mode is selected.
[Weight value at
0/4mA]
Input: Weight value Weight value at which the analog output
should display 0mA.
or
Weight value at which the analog output
should display 4mA (for the analog range 4…
20mA).
[Weight value at
20mA]
Input: Weight value Weight value at which the analog output
should display 20mA.
[Adjust for 4mA] Input: Weight value Value at 4mA.
[Adjust for 20mA] Input: Weight value Value at 20mA.