12
KJ79M574H01
8. Specifications
Serie PEFY-M-VMA(2)(L)-A
M20VMA(L)-A M25VMA(L)-A M32VMA(L)-A M40VMA(L)-A M50VMA(L)-A
Stromquelle
Kühlleistung
*1
*1
kW 2,2/2,5 2,8/3,2 3,6/4,0 4,5/5,0 5,6/6,3
mm 250/700/732 250/700/732 250/700/732 250/900/732 250/900/732
Nettogewicht kg 21(20) 21(20) 21(20) 25(24) 25(24)
(Schwach-Mittel-Stark)
m
3
/min 6,0-7,5-8,5 6,0-7,5-8,5 7,5-9,0-10,5 10,0-12,0-14,0 12,0-14,5-17,0
Pa 35/50/70/100/150
*2
35/50/70/100/150
*2
35/50/70/100/150
*2
35/50/70/100/150
*2
35/50/70/100/150
*2
Schalldruckpegel
*5
(Schwach-Mittel-Stark) dB(A) 18-22-24 18-22-24 20-24-27 20-25-28 21-28-31
Filter Standardfilter
M63VMA(L)-A M71VMA(L)-A M80VMA(L)-A M100VMA(L)-A
Stromquelle
Kühlleistung
*1
*1
kW 7,1/8,0 8,0/9,0 9,0/10,0 11,2/12,5
mm 250/1100/732 250/1100/732 250/1100/732 250/1400/732
Nettogewicht kg 27(26) 30(29) 30(29) 37(36)
(Schwach-Mittel-Stark)
m
3
/min 13,5-16,0-19,0 14,5-18,0-21,0 14,5-18,0-21,0 23,0-28,0-32,0
Pa 35/50/70/100/150
*2
40/50/70/100/150
*3
40/50/70/100/150
*3
40/50/70/100/150
*3
Schalldruckpegel
*5
(Schwach-Mittel-Stark) dB(A) 24-28-32 22-28-31 22-28-31 27-32-35
Filter Standardfilter
M125VMA(L)-A M140VMA(L)-A
Stromquelle
Kühlleistung
*1
*1
kW 14,0/16,0 16,0/18,0
mm 250/1400/732 250/1600/732
Nettogewicht kg 38(37) 42(41)
(Schwach-Mittel-Stark)
m
3
/min 28,0-34,0-37,0 29,5-35,5-40,0
Pa 40/50/70/100/150
*4
40/50/70/100/150
*4
Schalldruckpegel
*5
(Schwach-Mittel-Stark) dB(A) 31-35-37 30-34-37
Filter Standardfilter
M20VMA2-A M25VMA2-A M32VMA2-A M40VMA2-A M50VMA2-A
Stromquelle
Kühlleistung
*1
*1
kW 2,2/2,5 2,8/3,2 3,6/4,0 4,5/5,0 5,6/6,3
mm 250/1100/732 250/1100/732 250/1100/732 250/1100/732 250/1600/732
Nettogewicht kg 27 27 27 30 42
(Schwach-Mittel-Stark)
m
3
/min 13,5-16,0-19,0 13,5-16,0-19,0 13,5-16,0-19,0 14,5-18,0-21,0 29,5-35,5-40,0
Pa 35/50/70/100/150
*2
35/50/70/100/150
*2
35/50/70/100/150
*2
40/50/70/100/150
*3
40/50/70/100/150
*4
Schalldruckpegel
*5
(Schwach-Mittel-Stark) dB(A) 24-28-32 24-28-32 24-28-32 22-28-31 30-34-37
Filter Standardfilter
M63VMA2-A M71VMA2-A M80VMA2-A M100VMA2-A M125VMA2-A
Stromquelle
Kühlleistung
*1
*1
kW 7,1/8,0 8,0/9,0 9,0/10,0 11,2/12,5 14,0/16,0
mm 250/1600/732 250/1600/732 250/1600/732 250/1600/732 250/1600/732
Nettogewicht kg 42 42 42 42 42
(Schwach-Mittel-Stark)
m
3
/min 29,5-35,5-40,0 29,5-35,5-40,0 29,5-35,5-40,0 29,5-35,5-40,0 29,5-35,5-40,0
Pa 40/50/70/100/150
*4
40/50/70/100/150
*4
40/50/70/100/150
*4
40/50/70/100/150
*4
40/50/70/100/150
*4
Schalldruckpegel
*5
(Schwach-Mittel-Stark) dB(A) 30-34-37 30-34-37 30-34-37 30-34-37 30-34-37
Filter Standardfilter
*1
*2
*3
*4
*5