Why does my Mitsubishi Electric Air Conditioner Accessory motor not run at the correct speed?
- CCameron KnightAug 18, 2025
The motor speed might be incorrect due to several reasons: * The speed command from the controller might be incorrect or affected by noise. Ensure the speed command is correct and implement EMC measures. * There might be a difference between the command speed and the speed recognized by the inverter. Readjust the bias and gain Pr.125, Pr.126, C2 to C7, C12 to C15 of the speed command. * The setting for the number of encoder pulses could be incorrect. Check the settings of Pr.369 (Pr.851) under Vector control. * The motor constant might vary due to an increase in motor temperature. Enable online auto tuning at startup (set Pr.95 (Pr.574) = "1") under Real sensorless vector control. For a lift, use of the Start-time tuning start external input (X28) signal is recommended.