EasyManua.ls Logo

Mitsubishi Electric FR-E740-11K - User Manual

Mitsubishi Electric FR-E740-11K
332 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
3
4
5
6
7
1
2
FR-E700
INSTRUCTION MANUAL (Applied)
INVERTER
PRECAUTIONS FOR USE
OF THE INVERTER
PARAMETERS
TROUBLESHOOTING
PRECAUTIONS FOR
MAINTENANCE AND INSPECTION
SPECIFICATIONS
OUTLINE
WIRING
MODEL
MODEL
CODE
1A2-P26
FR-E700
INSTRUCTION MANUAL (Applied)
FR-E720-0.1K to 15K
FR-E740-0.4K to 15K
FR-E720S-0.1K to 2.2K
FR-E710W-0.1K to 0.75K
IB(NA)-0600277ENG-D (0812)MEE Printed in Japan Specifications subject to change without notice.
FR-E700 INVERTER INSTRUCTION MANUAL (Applied)
D

Table of Contents

Questions and Answers

  • C
    Christina SuttonSep 10, 2025
    How to unlock password on Mitsubishi Electric FR-E740-11K Inverter?
    • C
      Cody ReyesSep 12, 2025
      If the Mitsubishi Electric Inverter is password locked, enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.
  • A
    Autumn McdowellAug 25, 2025
    How to resolve overcurrent trip during deceleration or stop on Mitsubishi Electric FR-E740-11K?
    • J
      John ThomasAug 26, 2025
      If the Mitsubishi Electric Inverter experiences an overcurrent trip during deceleration or stop, it signifies that an overcurrent has occurred during these phases. Here’s what you can do: * Increase the deceleration time. * Check the wiring for output short circuits or ground faults. * Verify that the mechanical brake isn't activating too early. * Lower the stall prevention operation level. * Activate the stall prevention operation and the fast-response current limit operation (Pr.156). * If the motor is coasting, stop it before issuing a start command. Alternatively, use the automatic restart after instantaneous power failure/flying start function.
  • D
    darrellmillerAug 27, 2025
    How to fix regenerative overvoltage trip during deceleration or stop on Mitsubishi Electric FR-E740-11K Inverter?
    • T
      Tammy RayAug 27, 2025
      If your Mitsubishi Electric Inverter is tripping due to regenerative overvoltage during deceleration or stop, it means overvoltage has occurred. Try these solutions: * Increase the deceleration time to match the load's moment of inertia. * Make the brake cycle longer. * Use the regeneration avoidance function (Pr. 882, Pr. 883, Pr.885, Pr.886). * Consider using a brake resistor, brake unit, or power regeneration common converter (FR-CV) as needed.
  • J
    James HebertAug 27, 2025
    How to resolve regenerative overvoltage trip during acceleration on Mitsubishi Electric FR-E740-11K Inverter?
    • D
      David WalkerAug 27, 2025
      If your Mitsubishi Electric Inverter is tripping due to regenerative overvoltage during acceleration, it means overvoltage has occurred during acceleration. Here are some steps to take: * Decrease the acceleration time. * Implement the regeneration avoidance function using parameters Pr. 882, Pr. 883, Pr.885, and Pr. 886. * Ensure that the stall prevention operation level (Pr. 22) is set correctly.
  • E
    Emily QuinnAug 29, 2025
    What to do if Mitsubishi Electric FR-E740-11K Inverter shows inverter overload trip?
    • B
      Betty RothAug 29, 2025
      If the Mitsubishi Electric Inverter experiences an overload trip (electronic thermal O/L relay function), it signifies that the electronic thermal relay function for inverter element protection has been activated. To address this: * Increase the acceleration time. * Adjust the torque boost setting (Pr. 0). * Configure the load pattern selection setting (Pr. 14) according to the machine's load pattern. * Reduce the load. * Ensure the surrounding air temperature is within specified limits.
  • S
    schmidtjenniferNov 20, 2025
    How to fix overcurrent trip during acceleration on Mitsubishi Electric Inverter?
    • M
      Michael BowmanNov 21, 2025
      If the Mitsubishi Electric Inverter experiences an overcurrent trip during acceleration, it means that an overcurrent has occurred. To resolve this, try the following: * Increase the acceleration time. * Check for output short circuits or ground faults in the wiring. * If 'E.OC1' appears consistently at start, disconnect and restart the inverter. If the problem persists, the inverter may be faulty and you should contact your sales representative. * Ensure the base frequency is correctly set (Pr. 3) for your motor (50Hz). * Reduce the stall prevention operation level and activate both stall prevention and fast-response current limit operations (Pr.156). * For regenerative driving, adjust the base voltage in Pr. 19. * If the motor is coasting, stop it before issuing a start co...
  • H
    hrodriguezSep 18, 2025
    What does fan alarm mean on Mitsubishi Electric Inverter?
    • K
      Kevin RichardsonSep 18, 2025
      If the Mitsubishi Electric Inverter triggers a fan alarm, it indicates that the cooling fan is at a standstill or has decelerated. Check for fan failure and contact your sales representative.
  • J
    Jasmine WilliamsSep 22, 2025
    What to do if Mitsubishi Electric Inverter shows brake transistor alarm detection?
    • D
      Dustin JacksonSep 22, 2025
      If the Mitsubishi Electric Inverter detects a fault in the brake circuit, such as a brake transistor breakage, replace the inverter.
  • H
    howard51Sep 8, 2025
    What causes output phase loss in Mitsubishi Electric Inverter?
    • D
      dylan36Sep 9, 2025
      If the Mitsubishi Electric Inverter detects a loss in one of the three output phases (U, V, W) during operation, ensure the cables are properly wired. If the motor capacity is smaller than the inverter capacity, choose matching inverter and motor capacities.
  • B
    bwhiteSep 5, 2025
    What to do if Mitsubishi Electric Inverter shows regenerative brake pre-alarm?
    • J
      Jerry GarnerSep 6, 2025
      If the Mitsubishi Electric Inverter's regenerative brake duty reaches 85% of the Pr. 70 Special regenerative brake duty setting or higher, set a longer deceleration time and check the settings of Pr.30 Regenerative function selection and Pr. 70 Special regenerative brake duty.