FR-E700
INSTRUCTION MANUAL (Applied)
INVERTER
PRECAUTIONS FOR USE
OF THE INVERTER
PARAMETERS
TROUBLESHOOTING
PRECAUTIONS FOR
MAINTENANCE AND INSPECTION
SPECIFICATIONS
OUTLINE
WIRING
MODEL
MODEL
CODE
1A2-P26
FR-E700
INSTRUCTION MANUAL (Applied)
FR-E720-0.1K to 15K
FR-E740-0.4K to 15K
FR-E720S-0.1K to 2.2K
FR-E710W-0.1K to 0.75K
IB(NA)-0600277ENG-D (0812)MEE Printed in Japan Specifications subject to change without notice.
FR-E700 INVERTER INSTRUCTION MANUAL (Applied)
D

Table of Contents

Questions and Answers

  • J
    Jeffrey GordonSep 10, 2025
    How to unlock password on Mitsubishi Electric FR-E740-1.5K Inverter?
    • R
      rodney60Sep 12, 2025
      If the Mitsubishi Electric Inverter is password locked, enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.
  • S
    Suzanne ColeAug 25, 2025
    How to resolve overcurrent trip during deceleration or stop on Mitsubishi Electric Inverter?
    • W
      wwatkinsAug 26, 2025
      If the Mitsubishi Electric Inverter experiences an overcurrent trip during deceleration or stop, it signifies that an overcurrent has occurred during these phases. Here’s what you can do: * Increase the deceleration time. * Check the wiring for output short circuits or ground faults. * Verify that the mechanical brake isn't activating too early. * Lower the stall prevention operation level. * Activate the stall prevention operation and the fast-response current limit operation (Pr.156). * If the motor is coasting, stop it before issuing a start command. Alternatively, use the automatic restart after instantaneous power failure/flying start function.
  • M
    Mathew HansenAug 27, 2025
    How to fix regenerative overvoltage trip during deceleration or stop on Mitsubishi Electric Inverter?
    • R
      Richard GrossAug 27, 2025
      If your Mitsubishi Electric Inverter is tripping due to regenerative overvoltage during deceleration or stop, it means overvoltage has occurred. Try these solutions: * Increase the deceleration time to match the load's moment of inertia. * Make the brake cycle longer. * Use the regeneration avoidance function (Pr. 882, Pr. 883, Pr.885, Pr.886). * Consider using a brake resistor, brake unit, or power regeneration common converter (FR-CV) as needed.
  • J
    Jonathan BergAug 27, 2025
    How to resolve regenerative overvoltage trip during acceleration on Mitsubishi Electric Inverter?
    • D
      Dana EnglishAug 28, 2025
      If your Mitsubishi Electric Inverter is tripping due to regenerative overvoltage during acceleration, it means overvoltage has occurred during acceleration. Here are some steps to take: * Decrease the acceleration time. * Implement the regeneration avoidance function using parameters Pr. 882, Pr. 883, Pr.885, and Pr. 886. * Ensure that the stall prevention operation level (Pr. 22) is set correctly.
  • F
    Francisco LawrenceAug 29, 2025
    What to do if Mitsubishi Electric Inverter shows inverter overload trip?
    • M
      Matthew Whitehead PhDAug 29, 2025
      If the Mitsubishi Electric Inverter experiences an overload trip (electronic thermal O/L relay function), it signifies that the electronic thermal relay function for inverter element protection has been activated. To address this: * Increase the acceleration time. * Adjust the torque boost setting (Pr. 0). * Configure the load pattern selection setting (Pr. 14) according to the machine's load pattern. * Reduce the load. * Ensure the surrounding air temperature is within specified limits.
  • P
    Patrick VasquezNov 20, 2025
    How to fix overcurrent trip during acceleration on Mitsubishi Electric FR-E740-1.5K?
    • S
      Sharon WheelerNov 21, 2025
      If the Mitsubishi Electric Inverter experiences an overcurrent trip during acceleration, it means that an overcurrent has occurred. To resolve this, try the following: * Increase the acceleration time. * Check for output short circuits or ground faults in the wiring. * If 'E.OC1' appears consistently at start, disconnect and restart the inverter. If the problem persists, the inverter may be faulty and you should contact your sales representative. * Ensure the base frequency is correctly set (Pr. 3) for your motor (50Hz). * Reduce the stall prevention operation level and activate both stall prevention and fast-response current limit operations (Pr.156). * For regenerative driving, adjust the base voltage in Pr. 19. * If the motor is coasting, stop it before issuing a start co...
  • J
    Jessica HansonSep 18, 2025
    What does fan alarm mean on Mitsubishi Electric Inverter?
    • D
      Donna Martin MDSep 18, 2025
      If the Mitsubishi Electric Inverter triggers a fan alarm, it indicates that the cooling fan is at a standstill or has decelerated. Check for fan failure and contact your sales representative.
  • B
    Brianna WolfSep 23, 2025
    What to do if Mitsubishi Electric FR-E740-1.5K Inverter shows brake transistor alarm detection?
    • E
      Eric PowersSep 23, 2025
      If the Mitsubishi Electric Inverter detects a fault in the brake circuit, such as a brake transistor breakage, replace the inverter.
  • W
    Wendy MartinezSep 9, 2025
    What causes output phase loss in Mitsubishi Electric FR-E740-1.5K Inverter?
    • L
      leedavidSep 9, 2025
      If the Mitsubishi Electric Inverter detects a loss in one of the three output phases (U, V, W) during operation, ensure the cables are properly wired. If the motor capacity is smaller than the inverter capacity, choose matching inverter and motor capacities.
  • T
    timothy50Sep 6, 2025
    What to do if Mitsubishi Electric FR-E740-1.5K Inverter shows regenerative brake pre-alarm?
    • T
      Teresa HenrySep 6, 2025
      If the Mitsubishi Electric Inverter's regenerative brake duty reaches 85% of the Pr. 70 Special regenerative brake duty setting or higher, set a longer deceleration time and check the settings of Pr.30 Regenerative function selection and Pr. 70 Special regenerative brake duty.

Summary

WIRING

Wiring

Basic wiring procedures, including terminal connections and precautions for noise prevention.

PRECAUTIONS FOR USE OF THE INVERTER

EMC and leakage currents

Measures to suppress electromagnetic noise and handle leakage currents, including selection of earth leakage current breakers.

Precautions for use of the inverter

General safety precautions for handling, wiring, installation, and operation to prevent damage or injury.

Failsafe of the system which uses the inverter

Methods for providing system failsafe by using inverter status output signals and external backup systems.

PARAMETERS

Parameter list

Comprehensive list of all inverter parameters, their settings, functions, and related pages for detailed information.

Selection and protection of a motor

Parameters for motor overheat protection, applied motor settings, and offline auto-tuning for optimal performance.

Motor brake and stop operation

Parameters for configuring DC injection brake, regenerative brake, and various stop-on-contact control functions.

Operation selection at power failure and instantaneous power failure

Settings for automatic restart and power failure deceleration functions to ensure continuous operation.

Operation setting at fault occurrence

Functions for handling faults, including retry operation, phase loss protection, and ground fault detection.

Misoperation prevention and parameter setting restriction

Functions to prevent misoperation, such as reset selection, parameter write disable, and PU stop.

Selection of operation mode and operation location

Options for selecting the inverter's operation mode and controlling it via external signals, PU, or network.

Communication operation and setting

Details on communication setup using PU connector, USB, RS-485, and Modbus RTU protocols.

TROUBLESHOOTING

Reset method of protective function

Methods to reset protective functions, including inverter reset using the operation panel, power cycle, or RES signal.

List of fault or alarm indications

A comprehensive list of all fault and alarm indications displayed on the operation panel, with references to relevant pages.

Causes and corrective actions

Detailed explanations of common causes for errors, warnings, and faults, along with corresponding corrective actions.

PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Inspection items

Guidelines for daily and periodic inspections to identify potential faults and ensure reliable operation.

SPECIFICATIONS

Rating

Electrical ratings, applicable motor capacities, and output characteristics for different inverter models.

Mitsubishi Electric FR-E740-1.5K Specifications