4 SAFETY FB SPECIFICATIONS
4.14 M+SF_TSSEN_R
99
4
8004H External Function Test The automatic sensor test was faulty. An external manual
sensor test is necessary. (i_bNoExternalTest is OFF.)
A negative signal (i_bS_OSSD_In) edge at the sensor is
required.
o_bReady: ON
o_bS_OSSD_Out: OFF
o_bS_TestOut: ON
o_bTestPossible: OFF
o_bTestExecuted: OFF
o_bError: OFF
Generate a safety demand (e.g. across the
beam of the sensor).
8005H ESPE Interrupted External
Tes t
The automatic sensor test was faulty. An external manual
sensor test is necessary. (i_bNoExternalTest is OFF.) An
ON feedback signal (i_bS_OSSD_In) from the sensor is
required.
o_bReady: ON
o_bS_OSSD_Out: OFF
o_bS_TestOut: ON
o_bTestPossible: OFF
o_bTestExecuted: OFF
o_bError: OFF
Remove the safety demand from the sensor.
8006H End External Test The external manual test is complete.
o_bReady: ON
o_bS_OSSD_Out: OFF
o_bS_TestOut: ON
o_bTestPossible: OFF
o_bTestExecuted: OFF
o_bError: OFF
Set i_bReset to ON.
8010H ESPE Free No Test The FB has not detected a safety demand. (The sensor has
not been tested automatically.)
o_bReady: ON
o_bS_OSSD_Out: ON
o_bS_TestOut: ON
o_bTestPossible: ON
o_bTestExecuted: OFF
o_bError: OFF
Execute the automatic test by setting
i_bS_StartReset to ON.
8020H Test Request The automatic sensor test is active.
The light of sensors is stopped (o_bS_TestOut is set to
OFF), and the testing time to wait for the OFF OSSD signal
of sensors (i_bS_OSSD_In is set to OFF) is monitored (first
time).
o_bReady: ON
o_bS_OSSD_Out: ON
o_bS_TestOut: OFF
o_bTestPossible: OFF
o_bTestExecuted: OFF
o_bError: OFF
None.
8030H Test Active The automatic sensor test is active.
The light of sensors is restarted (o_bS_TestOut is set to
ON), and the testing time to wait for the ON OSSD signal of
sensors (i_bS_OSSD_In is set to ON.) is monitored (second
time).
o_bReady: ON
o_bS_OSSD_Out: ON
o_bS_TestOut: ON
o_bTestPossible: OFF
o_bTestExecuted: OFF
o_bError: OFF
8000H ESPE Free Test OK The FB has not detected a safety demand. (The sensor was
automatically tested.)
o_bReady: ON
o_bS_OSSD_Out: ON
o_bS_TestOut: ON
o_bTestPossible: ON
o_bTestExecuted: ON
o_bError: OFF
None.
In order to carry out the automatic sensor
test again, change i_bStartTest from OFF to
ON.
o_wDiagCode
(Hexadecimal)
State name Description, output setting Action