Flow temp. controller
C-19
Switch setting (FTC)
Flow temp. controller
4
C-19
FTC
Set the dip switch on the FTC (PCB) according to the following table.
System ON/OFF
Input
Change mode
Input
Change TEMP.
Input
Outdoor unit *4 SW1-1 SW1-2 SW1-5 SW1-6 SW6-1 SW6-2
BASIC External input
(non-voltage contact)
External input
(non-voltage contact)
DIP switch on PCB
SW2-1~8, SW3-1~3
SPLIT type ON OFF OFF ON OFF OFF
PACKAGED type ON OFF ON ON OFF OFF
External input
(non-voltage contact)
External input
(non-voltage contact)
Wired remote controller SPLIT type ON OFF OFF OFF OFF OFF
PACKAGED type ON OFF ON OFF OFF OFF
ANALOG
TEMP.
External input or
4-20mA *1
External input
(non-voltage contact)
4-20mA SPLIT type OFF ON OFF OFF ON ON
PACKAGED type OFF ON ON OFF ON ON
External input or
1-5V *2
External input
(non-voltage contact)
1-5V SPLIT type OFF ON OFF OFF OFF ON
PACKAGED type OFF ON ON OFF OFF ON
External input External input
(non-voltage contact)
0-10V SPLIT type ON ON OFF OFF OFF OFF
PACKAGED type ON ON ON OFF OFF OFF
BASIC
and
SIMPLE
External input and
*3
Wired remote controller
External input and
*3
Wired remote controller
DIP switch on PCB
SW2-1~8, SW3-1~3
SPLIT type OFF OFF OFF ON OFF OFF
PACKAGED type OFF OFF ON ON OFF OFF
External input and
*3
Wired remote controller
External input and
*3
Wired remote controller
Wired remote controller SPLIT type OFF OFF OFF OFF OFF OFF
PACKAGED type OFF OFF ON OFF OFF OFF
SIMPLE Wired remote controller Wired remote controller Wired remote controller SPLIT type OFF OFF OFF OFF OFF OFF
PACKAGED type OFF OFF ON OFF OFF OFF
*1: 4-20mA····OFF: 0~2mA
*2: 1-5V····OFF: 0~0.5V
*3: The command from the external input is prior to the one from the wired remote controller.
*4: SPLIT type : the standard outdoor unit without a plate HEX(refrigerant-water) inside.
PACKAGED type : the Air to Water outdoor unit with a plate of HEX(refrigerant-water) inside
OTHER SWITCH SETTING
SW1-3 Prohibition of Cooling mode
SW1-3=OFF : Operation mode Heating/HeatingECO/HotWater/Anti-freeze/Cooling
SW1-3=ON : Operation mode Heating/HeatingECO/HotWater/Anti-freeze
SW1-4 SW3-4,5,8 Not in use. Set to OFF. (Initial setting)
SW3-7 Not in use. Set to ON. (Initial setting)
SW3-6 Logic of Forced Comp. OFF external signal(TB142 5-6)
SW3-6 TB142 No.5-6 input Item
OFF
OFF(open) Normal
ON(short) Forced Comp. OFF
ON
OFF(open) Forced Comp. OFF
ON(short) Normal
SW1-6,7,8 Set temperature range
SW1-6=OFF Set temperature range with wired remote controller
SW1-6=ON Set temperature table with DIP switch of FTC
SW1-6 SW1-7 SW1-8 Temperature range with wired remote controller Temperature table
SW2-1~8, SW3-1~3
Heating/HeatingECO/Hot Water Anti-Freeze Cooling
OFF OFF OFF Upper 55 ˚C / lower 20 ˚C Upper 45 ˚C / lower 5 ˚C Upper 25 ˚C / lower 5 ˚C—
OFF ON OFF Upper 60 ˚C / lower 20 ˚C *1 Upper 45 ˚C / lower 5 ˚C Upper 25 ˚C / lower 5 ˚C—
OFF OFF ON Upper 50 ˚C / lower 20 ˚C Upper 45 ˚C / lower 5 ˚C Upper 25 ˚C / lower 5 ˚C—
OFF ON ON — — — —
ON OFF OFF — — — Table
1
ON ON OFF — — — Table
2
ON OFF ON — — — —
ON ON ON — — — —
*1. Do not use this setting when you use the standard outdoor unit without a plate HEX(Refrigerant-water) inside.
Photo. 4-1
TB61
TH1
TH2
SW1
SW6
SW2