21
4.5Connectinginputs/outputs
For multiple outdoor units control with FTC (Slave), see section 9.
FTC (Master)
1 2
3
4
5
6
+ - + - + -
Analog input
(0.5 - 3.5V)
5VDC
GND
12
13
14
TBI.3
IN10IN9IN8 IN1A
1
3
CN3C
(BLU)
1
3
CNPWM
(WHT)
LED1
LED2
LED3
LED4
CN108
5
1
5
1
5
1
CNRF
(WHT)
CN105
(RED)
TBO.1
TBO.2
TBO.3
TBO.4
CNP1
(WHT)
CNP4
(RED)
CNV1
(WHT)
CNIT
(BLU)
CN01
(WHT)
F2 F1
6.3A 250V 10A 250V
SW1
SW2
SW3
SW4
SW5
1
8
1
8
1
1
5
1
3
1
3
8
1
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
TBO.5
1
2
3
4
5
6
7
8
1
2
3
4
5
6
8
1
6
1
2
4
6
1
2
1
2
CNBHT
(BLK)
1
3
1
3
CNIH
(ORN)
1
4
1
3
CNW5
(WHT)
CN21
(YLW)
CNW12
(RED)
CN20
(RED)
TBI.2
126 10
14
8
137 119
4
53
2
1
TBI.3
2 4 6 8 1012 14
1
3
5
7 9
11
13
1
4
CN1A
(WHT)
2 4 6 8 10 1214
1
3
5
7 9
11
13
TBI.1
4. Electrical work
When the wires are wired to adjacent terminals
use ring terminals and insulate the wires.
Signal inputs
Item Name Modelandspecications
Signal input
function
Signal input
wire
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.13 mm² to 1.25 mm²
Solid wire: ø0.4 mm to ø1.2 mm
Switch Non-voltage “a” contact signals
Remote switch: minimum applicable load 12V DC, 1mA
Wiringspecicationandlocalsupplyparts
Name Terminal block Connector Item OFF (Open) ON (Short)
IN1 TBI.1 13-14 — Room thermostat 1 input *1 Refer to SW2-1 in <5.1 DIP Switch Functions>.
IN2 TBI.1 11-12 — Flow switch 1 input Refer to SW2-2 in <5.1 DIP Switch Functions>.
IN3 TBI.1 9-10 — Flow switch 2 input (Zone1) Refer to SW3-2 in <5.1 DIP Switch Functions>.
IN4 TBI.1 7-8 — Demand control input Normal Heat source OFF/ Boiler operation *3
IN5 TBI.1 5-6 — Outdoor thermostat input *2 Standard operation Heater operation/ Boiler operation *3
IN6 TBI.1 3-4 — Room thermostat 2 input *1 Refer to SW3-1 in <5.1 DIP Switch Functions>.
IN7 TBI.1 1-2 — Flow switch 3 input (Zone2) Refer to SW3-3 in <5.1 DIP Switch Functions>.
IN8 TBI.3 1-2 — Electric energy meter 1
*4IN9 TBI.3 3-4 — Electric energy meter 2
IN10 TBI.3 5-6 — Heat meter
IN11 TBI.3 7-8 —
Smart grid ready input *5
IN12 TBI.3 9-10 —
IN1A TBI.3 12-14 CN1A Flow sensor input *6
*1. Set the ON/OFF cycle time of the room thermostat for 10 minutes or more; otherwise the compressor may be damaged.
*2. If using outdoor thermostat for controlling operation of heaters, the lifetime of the heaters and related parts may be reduced.
*3. To turn on the boiler operation, use the main remote controller to select “Boiler” in “External input setting“ screen in the service menu.
*4. Connectable electric energy meter and heat meter
● Pulse type Voltage free contact for 12VDC detection by FTC (TBI.3 1, 3 and 5 pin have a positive voltage.)
● Pulse duration Minimum ON time: 40ms
Minimum OFF time: 100ms
● Possible unit of pulse 0.1 pulse/kWh 1 pulse/kWh 10 pulse/kWh
100 pulse/kWh 1000 pulse/kWh
Those values can be set by the main remote controller. (Refer to the menu tree in "7.2 Main remote controller".)
*5. As for the smart grid ready, refer to "4.9 Smart grid ready".
*6. Connectable ow sensor
● Power supply 5V DC
● Measuring range 5 to 100 L/min
Those values can be set by the main remote controller. (Refer to <Auxiliary setting> on Page 44.)
● Flow signal 0.5V (at minimum ow rate) to 3.5V (at maximum ow rate)
<Fig. 4.5.1>