Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
System Designation: Schedule No.:
Cooling*
Rated Capacity...............................17,200 Btu/h
Total Input.........................................90 W
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.74 A
Heating*
Rated Capacity...............................20,100 Btu/h
Total Input.........................................70 W
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.63 A
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.
Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.
(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB /
43ºF (6ºC) WB.
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
MCA .............................................. 1 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ............................DC 24V
Indoor Unit: SEZ-KD18NA
Fan
Type x Quantity............................ Sirocco Fan x 4
Motor .....................Direct-driven DC Brushless Motor
Motor Output.......................................96 W
Airow (Lo - Med - Hi)...................423 - 529 - 635 CFM
Air Filter ........................ Polypropylene Honeycomb
External Static Pressure...........0.02 - 0.06 - 0.14 - 0.20"WG
Sound Pressure Level (Lo - Med - Hi) .........30 - 34 - 38 dB(A)
W 46-7/8 / 1,190
D 27-9/16 / 700
H 7-7/8 / 200
Weight. ................................... 60 lbs. / 27 kg
Field Drainpipe Size O.D......................1-1/4" / 32 mm
Wall-mounted Remote Controller
................. PAR-21MAA
(See Data Submittal Sheet)
Refrigerant Type
.................................. R410A
Refrigerant Pipe Size O.D.
Gas Side
.................................1/2" / 12.7 mm
Liquid Side
................................1/4" / 6.35 mm
Connection Method
................................Flared
Remote Controller: PAR-21MAA
• M-NET Control Adapter (MAC-399IF)
• External Heat Adapter (PAC-YU25HT)
• CN24 Relay Kit (CN24RELAY-KIT-CM)
• Three-pole Disconnect Switch (TAZ-MS303)
• Ceiling-concealed ducted indoor unit for residential applications
• Ultra thin body: 7-7/8" high
• Built-in drain mechanism for condensate removal; lifts to 21-11/16"
• Air lter is included with indoor unit
• Quiet operation ― as low as 23 dBA
• PAR-21MAA wired remote controller is included
• Indoor unit powered from outdoor unit using A-Control
• Automatic fan speed control
• Auto restart following a power outage
• Limited warranty: one year on parts and defects
• All Horizontal-ducted Indoor Units:
• Select Wall-mounted Indoor Units:
and
• A combination of both Horizontal-ducted
and Wall-mounted Indoor Units
Refer to the separate submittal forms for the
MSZ-A and MSZ-FD Indoor Units and MXZ
Outdoor Units.
Horizontal-ducted Indoor Unit: SEZ-KD-NA
Remote Controller
PAR-21MAA -
Packaged with SEZ
Wall-mounted Indoor Unit: MSZ-A09, 12, 15, 17, 24NA
Wireless Remote Controller -
Packaged with MSZ-A and MSZ-FD
(Optional Wired Remote Controller
PAR-21MAA)
Outdoor Unit: MXZ-3A30NA
Wall-mounted Indoor Unit: MSZ-FD-NA