Mitsubishi Heavy Industries SCM71ZM-S1 - (12) Current cut; (13) Outdoor unit failure; (14) Discharge pipe sensor disconnection protection control

Mitsubishi Heavy Industries SCM71ZM-S1
379 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2) Control value
Model
Current safe
Current safe
Current safe
Cooling Heating Cooling Heating Cooling Heating
SCM71, 80ZM - S1
13.0 16.0 10.0 10.0 7.5 7.5
Unit: A
(14) Discharge pipe sensor disconnection protection control
(a) When the compressor command speed is other than 0 rps.
(i) Tho-D(10)
-
Tho-D(0) < 8 °C, and Tho-D(10)
-
Tho-A(10) < 5 °C
The compressor command speed is set on A rps for 5 minutes. After 5 minutes, the compressor command speed is set
on B rps for 5 minutes.
(ii) Tho-D(20)
-
Tho-D(15) < 5 °C :
The compressor command speed is set on 0 rps.
(b) Once the unit is stopped by this function, it is not restarted.
Notes (1) Tho-D(X): After compressor operation, the discharge pipe temperature sensor after X minutes.
(2) Tho-A(X): After compressor operation, the outdoor air temperature sensor after X minutes.
• Values of A, B
Model
A
B
20 rps
60 rps
SCM80ZM-S1
20 rps
60 rps
SCM71ZM-S1
(12) Current cut
(a) Purpose:
(b) Detail of operation:
(13)
Outdoor unit failure
(23) Indoor fan motor protection
compressor command
(SRF:150)
300
-
Note (1) When the jumper wire (J32) on the outdoor unit sub-PCB is short-circuited (factory default), this control is performed only at initial operation after turn-
ing the power source on. If the jumper wire (J32) is open, this control is not performed.
-
200
-
'17 • SCM-T-225