4. CONNECTING PIPING WORK
1. Restrictions on unit installation
Abide by the following restrictions on unit installation.
Improper installation can cause compressor failure or performance degradation.
Dimensional restrictions
Model SRC20/25/35
Model SRC40/50/60
Connecting pipe length(L) 25m or less 30m or less
Elevation difference between
indoor and outdoor units(H)*
15m or less 20m or less
* Outdoor unit installation position can be higher as well as lower than the indoor unit installation position.
2. Preparation of connecting pipe
2.1. Selecting connecting pipe
Select connecting pipe according to the following table.
Model SRC20/25/35
Model SRC40/50/60
Gas pipe �9.52 �12.7
Liquid pipe �6.35 �6.35
.mm 8.0 ot lauqe ro naht retaerg eb tsum ssenkciht llaw epiP •
SCI ,51.040.32 SCI epip reppoc sselmaes dezidixoed surohpsohP( epyt-O eb tsum lairetam epiP •
77.150.30).
NOTE
GNITSIXE FO NOITAZILITU .5 ot refer ,metsys epip gnitcennoc gnitsixe eht esuer ot deriuqer si ti fI
PIPE.
2.2. Cutting connecting pipe
(1) Cut the connecting pipe to the required length with pipe cutter.
(2) Hold the pipe downward and remove the burrs. Make sure that no foreign material enters the pipe.
(3) Cover the connecting pipe ends with the tape.
3. Piping work
.desolc ylluf era sevlav ecivres sag dna diuqil htob taht kcehC
Carry out the piping work with service valves fully closed.
Liquid service valve
Gas service valve
3.1. Flaring pipe
(1) Take out fl are nuts from the service valves of outdoor unit and engage them onto connecting pipes.
(2) Flare the pipes according to table and fi gure shown below.
Flare dimensions for R32 are different from those for conventional refrigerant.
Although it is recommended to use the fl aring tools designed specifi cally for R32 or R410A, conventional
fl aring tools can also be used by adjusting the measurement of protrusion B with a fl are adjustment gauge.
Copper pipe
outer diameter
A
0
–0.4
Copper pipe
outer diameter
Rigid (clutch) type
R32 or
R410A
Conventional
�6.35 9.1 �6.35
0-0.5 1.0-1.5�9.52 13.2 �9.52
�12.7 16.6 �12.7
3.2. Connecting pipes
(1) Connect pipes on both liquid and gas sides.
(2) Tighten nuts to specifi ed torque shown in the table below.
Service valve size (mm) Tightening torque (N·m)
�6.35 (1/4") 14-18
�9.52 (3/8") 34-42
�12.7 (1/2") 49-61
Do not hold the valve cap area with a spanner
CAUTION
• Do not apply refrigerating machine oil to the fl ared surface. It can cause refrigerant leakage.
• Do not apply excess torque to the fl ared nuts. The fl ared nuts may crack resulting in refrigerant leakage.
4. Evacuation
trop ecivres ot dlofinam eguag fo esoh egrahc tcennoC .dlofinam eguag ot pmup muucav tcennoC )1(
of outdoor unit.
.)gH mc67–( aPM1.0- swohs eguag muucav eht retfa ruoh eno tsael ta rof pmup muucav eht nuR )2(
.erom ro setunim 51 rof tfel si metsys eht fi neve esir ton seod rotacidni eguag muucav eht taht mr finoC )3(
.tniop egakael a sah ro edisni tfel er
utsiom sah metsys eht fi esir lliw rotacidni eguag muucaV
.niaga )1( ot nruter dna ti riaper ,dnuof si tniop egakael fI .tniop egakael eht rof metsys eht kcehC
.pmup muucav eht pots dna oL eldnaH eht esolC )4(
ton seod retniop eguag erusserp dnuopmoc eht taht erus ekam ot setunim wef a rof etats siht peeK
swing back.
service valve. sag dna evlav ecivres diuqil morf spac evlav evomeR )5(
nepo ot yek hcnerw lanogaxeh a h
tiw esiwkcolcretnuoc eerged 09 dor s'evlav ecivres diuqil eht nruT )6(
valve.
Close it after 5 seconds, and check for gas leakage.
.sdor evlav dna era fl s'tinu roodtuo dna era fl s'tinu roodni morf egakael sag rof kcehc ,retaw ypaos gnisU
Wipe off all the water after completing the check.
ecivres sag dna diuqil nepo ylluf dna trop ecivres s'evlav ecivres sag morf esoh gnigrahc tcennocsiD )7(
valves. (Do not attempt to turn valve rod beyond its stop.)
.woleb elbat eht ni nwohs euqrot de fiiceps eht ot pac trop ecivres dna spac evlav ecivres nethgiT )8(
Service valve size (mm)
Service valve cap tightening
torque (N·m)
Service port cap tightening
torque (N·m)
�6.35 (1/4")
20-30
10-12�9.52 (3/8")
�12.7 (1/2") 25-35
Handle Lo
Valve cap
Liquid service valve
Gas service valve
Service port
Pressure gauge
Gauge manifold
Handle Hi
Vacuum pump
CAUTION
To prevent vacuum pump oil from entering into the refrigerant system, use a counterfl ow prevention adapter.
5. Additional refrigerant charge
Additional refrigerant charge is required only when connecting pipe length exceeds 15 m.
5.1 Calculating additional refrigerant charge
Additional refrigerant charge can be calculated using the formula given below.
Additional refrigerant charge (g) = { Connecting pipe length (m) – Factory charged length 15 (m) } x 20 (g/m)
NOTE
• If additional refrigerant charge calculation result is negative, there is no need to remove the refrigerant.
• If refrigerant recharge is required for the unit with connecting pipe length 15m or shorter, charge the
factory charged amount as shown in the table below.
• The maximum refrigerant charge amount is designed as shown in the table below.
Model SRC 20/25/35 Model SRC40/50/60
The factory refrigerant charge amount(kg) 1.20 1.30
The maximum refrigerant charge amount(kg) 1.40 1.60
5.2 Charging refrigerant
(1) Charge the R32 refrigerant in liquid phase from service port with both liquid and gas service valves
shut. Since R32 refrigerant must be charged in the liquid phase, make sure that refrigerant is dis-
charged from the cylinder in the liquid phase all the time.
(2) When it is diffi cult to charge a required refrigerant amount, fully open both liquid and gas service
valves and charge refrigerant, while running the unit in the cooling mode. When refrigerant is
charged with the unit being run, complete the charge operation within 30 minutes.
(3) Write the additional refrigerant charge calculated from the connecting pipe length on the label at-
tached on the service cover.
CAUTION
•
Running the unit with an insuffi cient quantity of refrigerant for a long time can cause unit malfunction.
•
Do not charge more than the maximum refrigerant amount. It can cause unit malfunction.
5. UTILIZATION OF EXISTING PIPE
(1) Check whether an existing pipe system is reusable or not by using the following fl ow chart.
Repair is impossible.
Air tightness is
impossible.
Repair is impossible.
Repair
Air tightness is OK.
Repair
Repair
NO
NO
NO
NO
NO
NO
NO
Are the outdoor and indoor units connected to the existing pipe system ?
Does the existing unit use any of the following refrigerant oils ?
Suniso, MS,Barell Freeze, HAB, Freol, ether oil, ester oil.
Do the existing pipe specifi cations (pipe length, pipe size and elevation difference between indoor and outdoor unit) conform to the restric-
tion of the unit.? (Go to 4.CONNECTING PIPING WORK and check 1.Restrictions on unit installation and 2.Preparation of connecting pipe.)
Is the existing pipe system free of gas leaks?
(Check whether refrigerant charge was required
frequently for the system before.)
Is the existing pipe system free of corrosion, fl aws and dents?
Are heat insulation materials of the existing pipe system
free of peel-off or deterioration?
(Heat insulation is necessary for both gas and liquid pipes.)
Is the existing piping system free of any loose pipe support ?
The existing pipe system is reusable.
The existing pipe system is not reusable.
Install the new pipe system.
Repair the damaged parts.
Check the pipe system for air tightness.
Repair the damaged parts.
Repair the loose pipe support.
NO
Is it possible to run the unit ?
YES
YES
YES
YES
YES
YES
YES
YES
NOTE
• Consult with our distributor in the area, if you need to recover refrigerant and charge it again.
(2) Clean the existing pipe system according to the procedure given below.
(a) Carry out forced cooling operation of existing unit for 30 minutes.
For ‘Forced cooling operation’ refer to the indoor unit installation manual.
(b) Stop the indoor fan and carry out forced cooling operation for 3 minutes (Liquid return).
(c) Close the liquid service valve of the outdoor unit and carry out pump down operation (Refer to 6.
PUMP DOWN).
(d) eht yb degrahcsid si rettam ngierof yna ro lio noitaregirfer derolocsid fI .sag negortin htiw wolB
blow, wash the pipe system or install a new pipe system.
(3) Remove the fl are nuts from the existing pipe system. Go back to 4.CONNECTING PIPING WORK
and proceed to step 2.2 Cutting connecting pipe.
CAUTION
)wen( eht htiw deilppus stun era fl eht taht erus ekaM .)tinu gnitsixe fo( stun era fl dlo eht esu ton oD •
outdoor unit are used.
siht neht moor / esuoh eht edisni detacol si tinu roodni eht ot noitcennoc noisserpmoc / dera fl eht fI •
pipework can’t be reused.
* If the existing piping is specifi ed as liquid pipe ø9.52 or gas pipe ø12.7, refer to the following. (SRC40,50
and 60 only)
<Table of pipe size restrictions>
Additional charge volume per meter of pipe 0.054kg/m
Pipe size
Liquid pipe ø9.52
Gas pipe ø12.7
Maximum one-way pipe length 10
Length covered without additional charge 5
Additional charge amount (kg) = {Main pipe length (m) - Length covered without additional
charge shown in the table (m)} X Additional charge amount per meter of pipe shown in the table (kg/m)
6. PUMP DOWN
(1) Connect charge hose of gauge manifold to service port of outdoor unit.
(2) Close the liquid service valve with hexagonal wrench key.
(3) Fully open the gas service valve with hexagonal wrench key.
(4) Carry out forced cooling operation (For forced cooling operation procedure, refer to indoor unit installation
manual).
(5) When the low pressure gauge becomes 0.01MPa, close the gas service valve and stop forced cooling
operation.
7. ELECTRICAL WIRING WORK
WARNING
• Make sure that all the electrical work is carried out in accordance with the national or regional electri-
cal standards.
• Make sure that the earth leakage breaker and circuit breaker of appropriate capacities are installed
(Refer to the table given below).
• Do not turn on the power until the electrical work is completed.
• Do not use a condensive capacitor for power factor improvement under any circumstances.
(It does not improve power factor. Moreover, it can cause an abnormal overheat accident).
Breaker specifications
Model
SRC20/25/35
SRC40/50/60
Main fuse specification
Model
SRC20/25/35 250V 15A
SRC40/50/60 250V 20A
1.Preparing cable
(1) Selecting cable
Select the power source cable and connecting cable in accordan
(a) Power source cable
3 cores* 2.5mm
When selecting the power source cable length, make sure that voltage drop is less than 2%.
If the wire length gets longer, increase the wire diameter.
(b) Connecting cable
4 cores* 1.5mm
* 1 Earth wire is included (Yellow/Green).
(2) Arrange each wire length as shown below.
Make sure that each wire is stripped 10mm from the end.
<Power source cable>
(3) Attach round crimp-type terminal to each wire as shown in the below.
Select the size of round crimp-type terminal after considering the specifications of terminal block and wire
diameter.
CAUTION
Power source cable and connecting cable must conform to the spe
Using cables with wrong specifi
8. FINISHING WORK
1. Heating and condensation prevention
(1) Dress the connecting pipes (both liquid and gas pipes) with insulation to prevent it from heating
and dew condensation.
Use the heat insulating material which can withstand 120°C or higher temperature. Make sure that
insulation is wrapped tightly around the pipes and no gap is left between them.
(2) Wrap the refrigerant pipings of indoor unit with indoor unit heat insulation using tape.
(3) Cover the flare-connected joints (indoor side) with the indoor unit heat insulation and wrap it with
an insulation pad (standard accessory provided with indoor unit).
(4) Wrap the connecting pipes, connecting cable and drain hose with the tape.
(2)
NOTE
Locations where relative humidity exceeds 70%, both liquid and gas pipes need to be dressed with 20mm
thicker heat insulation materials.
CAUTION
• Improper insulation can cause condensate(water) formation during cooling operation.
Condensate can leak or drip causing damage to household property.
• Poor heat insulating capacity can cause pipe outer surface to reach high temperature during heating
operation. It can cause cable deterioration and personal injury.
9. INSTALLATION TEST CHECK POINTS
After finishing the installation work, check the following points again before turning on the power
Conduct test run (Refer to indoor unit installation manual) and ensure that the unit operates properly.
Power source voltage complies with the rated voltage of air-conditioner.
Earth leakage breaker and circuit breaker are installed.
Power cable and connecting cable are securely fixed to the terminal block.
Both liquid and gas service valves are fully open.