CAUTION
Please make sure that the service valves (gas, liquid) are full open before a test run. Conducing a test run with any
of them in a closed position can result in a compressor failure.
"0" : External operation input
"1" : Demand input
"2" : Cooling/heating forced input
"3" : Silent mode input 1
*1
"4" : Spare
"5" : Outdoor fan snow guard control input
"6" : Test run external input 1 (equivalent to SW5-1)
"7" : Test run external input 2 (equivalent to SW5-2)
"8" : Silent mode 2
*2
"9" : Spare
CnS1 closed
Operation permitted
Invalid
Heating
Valid
Valid
Test run start
Cooling test run
Valid
CnS1 opened
Operation prohibition
Valid
Cooling
Invalid
Invalid
Normal operation
Heating test run
Invalid
"0" : Operation output
"1" : Error output
"2" : Compressor ON output
"3" : Fan ON output
"4 – 9" : Spare
display panel. When a signal is input to CnS1, the following functions are enabled.
The external output function of CnZ1 can be changed by
changing the setting in P06 on the 7-segment display panel.
7-3. External input and output specifications.
Contents Specification Connector on PCB
External input CNS1 Non-voltage contact (DC12V) J.S.T(NICHIATSU) B02B-XAKS-1-T
External output CNZ1 DC12V output J.S.T(NICHIATSU) BH2P-VH-1-R
(1) Make sure that a measurement between the power source terminal block and ground, when measured with a 500V megger tester, is greater than 1 MΩ.
When the unit is left for a long time with power OFF or just after the installation, there is possibility that the refrigerant is accumulated in the compressor and the
insulation resistance between the contact terminals for power source and grounding decreases to 1MΩ or around.
When the insulation resistance is 1MΩ or more, the insulation resistance will rise with crank case heater power ON for 6 hours or more because the refrigerant in
the compressor is evaporated.
(2) Please check the resistance of the signaling line terminal block before power is turned on. If a resistance measurement is 100Ω or less, it suggests a possibility
that power cables are connected to the signaling line terminal block. (Please check wiring refer to section 6.ELECTRICAL WIRING WORK)
(3) Be sure to turn on the crank case heater 6 hours before operation.
(4) Make sure that the bottom of the compressor casing is warm. (Outdoor temperature + 5 or more)
(5) Be sure to fully open the service valves (liquid, gas) for the outdoor unit.
Operating the outdoor unit with the valves closed may damage the compressor.
(6) Check that the power to all indoor units has been turned on. If not, a failure may occur.
8. TEST OPERATION
Before beginning operation
It is recommended to practice the check operation before the test run.
(You may test run or perform normal operation even if the check operation is not performed.)
For details of check operation, refer to the technical manual.
Important:
Before starting the check operation, complete the address setting of indoor and outdoor units and the refrigerant charge.
You cannot check precisely unless proper quantity of refrigerant is charged.
You cannot perform the check operation when the system is stopped under abnormal condition.
You cannot perform the check operation when total capacity of connected indoor units is less than 80% of outdoor units.
You cannot perform the check operation if the communication protocol is previous SL.
Don’t perform the check operation at the same time on a plural number of refrigerant systems. You cannot check precisely.
Perform the check operation within the applicable temperature range (Outdoor air temperature: 0 - 43, indoor air temperature: 10 - 32). You cannot start the
check operation if it is out of the applicable temperature range.
You cannot check the fresh air ventilation indoor unit. (You can check indoor units other than the fresh air ventilation indoor unit on the same refrigerant system.)
You cannot performe the check operation if the connected indoor unit is only one in one refrigerant system.
You cannot performe the check operation if it is set at 0% in the demand mode or capacity save mode.
(1) Check item
Check operation allows confirming the following points.
Whether the service valve is closed or not (Open/close check)
Whether refrigerant pipes and signal line are connected properly on indoor/outdoor units or not (Mismatch check)
Whether the indoor unit expansion valve operates properly or not (Expansion valve failure check)
(2) Procedure of check operation
(a) Start of check operation
Check operation
*1 Switch valid/invalid depending
on the outdoor temperature.
*2 Any time valid not depending on
the outdoor temperature.