EasyManua.ls Logo

Mitsubishi FDC121KXZEN1-W - Page 29

Mitsubishi FDC121KXZEN1-W
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(1) To avoid mixing of different types of oil, use separate tools for each type of refrigerant.
(2) To avoid moisture from being absorbed by the ice machine oil, the time for when the refrigerant circuit is open should be kept as short as possible.
(Within 10 min. is ideal.)
(3) For other piping work, airtighteness testing , vacuuming, and refrigerant charging, refer to section 4, REFRIGERANT PIPING.
(4) Diagnostic Inspection Procedures
For the meanings of failure diagnosis messages, please refer to the technical manual.
(5) 7-segment LED indication
Data are indicated when so chosen with the indication selector switch. For the details of indication, please refer to the technical manual.
9. CAUTIONS FOR SERVICING (for R32 and compatible machines)
(2) Method of starting a test run for a cooling operation from an outdoor unit: please operate a remote control unit according to the following steps.
(a) Start of a cooling test run
Operate the unit by pressing the START/STOP button.
Select the “COOLING” mode with the MODE button.
Press the TEST RUN button for 3 seconds or longer.
The screen display will be switched from “Select with ITEM ”“Determine with SET ”“Cooling test run
.”
When the SET button is pressed while “Cooling test run
” is displayed, a cooling test run will start. The screen display will be switched to “COOLING TEST RUN.
(b) Termination of a cooling test run
When the START/STOP button or the “TEMP SET ” button is pressed, a cooling test run will be terminated.
(1) Test run from an outdoor unit.
Whether CnS1 is set to ON or OFF, you can start a test run by using the SW5-1 and SW5-2 switches provided on the outdoor unit PCB.
Select the test run mode first.
Please set SW5-2 to ON for a cooling test run or OFF for a heating test run. (It is set to OFF at the factory for shipment)
Turning SW5-1 from OFF to ON next will cause all connected indoor units to start.
When a test run is completed, please set SW5-1 to OFF.
Note: During a test run, an indoor unit cannot be operated from the remote control unit (to change settings). (“Under central control” is indicated)
Test operation
(2) Procedure of check operation
(a) Start of check operation
Confirm that all of SW3-7 (Forced cooling/heating mode), SW-5-1 (Test run), SW5-2 (Test run cooling setting) and SW5-3 (Pump-down operation) are turned OFF.
Change then SW3-5 (Check operation) OFFON to start the check operation.
It takes normally about 15 - 30 minutes from the start to the end of check operation. (Max. 80 minutes)
(b) Termination of check operation and result display
As the check operation terminates, the system stops automatically and displays the result on the 7-segment indicator.
<Normal termination>
“CHO End” is shown on the 7-segment indicator.
Return SW3-5 to OFF setting. 7-segment indicator returns to normal display.
<Termination by error>
Error is displayed on the 7-segment indicator.
Correct the abnormal condition referring to the “Check Point” column, and return SW3-5 to OFF.
Restart then the check operation from (2) (a).
Transfer
Use the instruction manual that came with the outdoor unit to explain the operation method to the customer.
Please ask the customer to keep this installation manual together with the user’s manual of his indoor units.
Instruct the customer that the power should not be turned off even if the unit is not to be used for a long time. This will enable operation of the air-conditioner any
time. (Since the compressor bottom is warmed by the crank case heater, seasonal compressor trouble can be prevented.)
*Errors other than the above may be indicated by the detection of error. In such occasion, correct the matter by referring to the technical manual.
*Code and Data are indicated alternately by 4-second intervals.
Data
Content
Code
H1
H2
CHO
Max. remaining time
Max. remaining time
End
Preparing for check operation. Indicates the maximum remaining time (minute).
Normal termination of check operation.
During the check operation. Indicates the maximum remaining time (minute).
7-segment display during check operation
Data Content
Check Point
Code
CHL
CHU
CHJ
CHE
CHE
– – –
– – –
Abnormal indoor unit No.
Abnormal indoor unit No.
Abnormal indoor unit No.
Display on 7-segment indicator after check operation
Service valve is closed.
(Refrigerant circuit is choked
somewhere.)
Mismatch of refrigrant
pipes/signal line.
Refrigerant is not circulated in
the abnormal indoor unit.
Expansion valve does not operate
properly on the abnormal indoor
unit.
Termination of check operation
by error
Termination of check operation
by error. Indicated indoor unit is
under abnormal condition.
Is the service valve of outdoor unit closed?
Is the low pressure sensor normal? (Detection pressure can be confirmed on 7-segment indicator.)
Is the coil connector of indoor unit expansion valve connected?
Is the expansion valve coil of indoor unit detached from the valve body?
Is the heat exchanger sensor of indoor unit normal? (Check for sensor disconnection.)
Are refrigerant pipes/signal line connected properly between indoor and outdoor units?
Is the coil connector of indoor unit expansion valve connected?
Is the expansion valve coil of indoor unit detached from the valve body?
Is the heat exchanger sensor of indoor unit normal? (Check for sensor disconnection.)
Is the coil connector of indoor unit expansion valve connected?
Is the expansion valve coil of indoor unit detached from the valve body?
Is the heat exchanger sensor of indoor unit normal? (Check for sensor disconnection.)
Is any error (E??) indicated on indoor or outdoor units?
Is signal line connected without loose?
Was any SW setting changed during check operation?
Is any error (E??) indicated on indoor or outdoor units?
Is signal line connected without loose?
Is the power source turned ON at the indoor unit side?
'20 • KX-T-373
-
27
-

Table of Contents

Related product manuals