To change setting Installation of the receiver
Preparation before installation
1. Change the setting of switches on the accessory PCB.
2. When SW1 is turned to OFF position, change the wireless remote control setting.
Setting to avoid mixed communication of
For the method of changing the setting, refer to
4
Wireless remote control
.
*For the receivable area of the signal, refer to
5
Receiver
.
WARNING
WARNING
Safety precautions
1
Accessories
•Please read this manual carefully before starting installation work to install the unit properly.
All of the following are important information to be observed strictly.
WARNING Failure to follow these instructions properly may result in serious consequences
such as death, severe injury, etc.
CAUTION Failure to follow these instructions properly may cause injury or property damage.
It could have serious consequences depending on the circumstances.
•The following symbols are used in the text.
Never do. Always follow the instructions given.
•
Keep this manual at a safe place where you can consult with whenever necessary. Show this manual to installers when
moving or repairing the unit. When the ownership of the unit is transferred, this manual should be given to the new owner.
• Consultyourdealeroraprofessionalcontractortoinstalltheunit.
Improper installation made on your own may cause electric shocks, fire or dropping of the unit.
•
Installationworkshouldbeperformedproperlyaccordingtothisinstallationmanual.
Improper installation work may result in electric shocks, fire or break-down.
• Besuretouseaccessoriesandspecifiedpartsforinstallationwork.
Use of unspecified parts may result in drop, fire or electric shocks.
• Installtheunitproperlytoaplacewithsufficientstrengthtoholdtheweight.
If the place is not strong enough, the unit may drop and cause injury.
•
Besuretohavetheelectricalwiringworkdonebyqualifiedelectricalinstaller,anduseexclusivecircuit.
Power source with insufficient and improper work can cause electric shock and fire.
• ShutOFFthemainpowersourcebeforestartingelectricalwork.
Otherwise, it could result in electric shocks, break-down or malfunction.
• Donotmodifytheunit.
It could cause electric shocks, fire, or break-down.
• BesuretoturnOFFthepowercircuitbreakerbeforerepairing/inspectingtheunit.
Repairing/inspecting the unit with the power circuit breaker turned ON could cause electric shocks or
injury.
• Donotinstalltheunitinappropriateenvironmentorwhereinflammablegascould
generate,flowin,accumulateorleak.
If the unit is used at places where air contains dense oil mist, steam, organic solvent vapor, corrosive gas (ammonium,
sulfuric compound, acid, etc) or where acidic or alkaline solution, special spray, etc. are used, it could cause electric
shocks, break-down, smoke or fire as a result of significant deterioration of its performance or corrosion.
•
Donotinstalltheunitwherewatervaporisgeneratedexcessivelyorcondensationoccurs.
It could cause electric shocks, fire, or break-down.
• Donotusetheunitinaplacewhereitgetswet,suchaslaundryroom.
It could cause electric shocks, fire, or break-down.
• Donotoperatetheunitwithwethands.
It could cause electric shocks.
• Donotwashtheunitwithwater.
It could cause electric shocks, fire, or break-down.
• Usethespecifiedcablesforwiring,andconnectthemsecurelywithcaretoprotect
electronicpartsfromexternalforces.
Improper connections or fixing could cause heat generation, fire, etc.
• When installing the unit atahospital, telecommunication facility, etc., take
measurestosuppresselectricnoises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private
power generator, high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment
could disrupt medical activities, video broadcasting or cause noise interference.
• DonotleavetheremotecontrolwithitsPCBcaseremoved.
If dew, water, insect, etc. enter through the hole, it could cause electric shocks, fire or break-down.
CAUTION
Please make sure that you have all of the following accessories.
2
Preparationbeforeinstallation(continued)
2
Preparation before installation
SettingofPCB
Accessory PCB has the following switches to set the functions. Default setting is shown with mark.
3
How to install the receiver
3
Howtoinstallthereceiver(continued)
It is possible to install the receiver by replacing the corner lid on the panel.
1
Connect the wire connector (Communication) to CNB on PCB.
2
Connect the wire connector (Receiver) to CN3 on PCB.
3
Install the PCB mounting supports on the bracket (Sheet metal).
4
Install PCB on the PCB mounting supports.
5
Insert the bracket (Sheet metal) in one side of control box, and fix the other side with screws as
shown in the figure.
6
Connect round terminals of wires (Communication) to the terminal block (X, Y) in the control box. The
wires have no polarity.
7
Fix wires with bands as shown in the figure.
8
Cut off the half-blanks on the panel (at 4 places) as shown in the figure.
9
Pass the wiring (Communication) through the opening on the panel.
:
Connect connectors of the wiring (Communication) and the receiver.
A
Install the receiver on the panel according to the installation manual of the panel.
B
Install the control box lid with care not to pinch wires, and fix with screws (2 pcs).
1
Remove the inlet grille according to the installation manual of the panel.
2
Remove the corner lid at the refrigerant pipe side.
3
Loosen screws (2 pcs) on the control box of the unit.
4
Slide the control lid in the arrow direction, and remove it.
PJF012D506
SW1
Prevents interference during multiple setting ON : Normal
OFF : Remote
SW2
Receiver master/slave setting ON : Master OFF : Slave
SW3
Buzzer ON : Valid OFF : Invalid
SW4
Auto restart ON : Valid OFF : Invalid
(1) Places exposed to direct sunlight (8) Places where the receiver is influenced by
fluorescent lamp (especially inverter
type) or sunlight
• Do not install the wireless kit at the following places in order to avoid malfunction.
It could cause break-down or deformation of remote control.
(2) Places near heat-generating devices
(3) High humidity places
(4) Hot surface or cold surface enough to (9) Places where the receiver is affected by infrared
generate condensation rays of any other communication devices
(5)
Places exposed to oil mist or steam directly
(10)
Places where some object may obstruct the
communication with the remote control
(6) Uneven surface
(7)
Places affected by the direct air flow of the AC unit
2
3
4
Screw for holder
Remote control holder
AAA dry cell battery (LR03)
2
5
User’s manual
1
2
1
1
Wireless remote control (RCN-E2)
1
①
Receiver 1
⑤
Bracket mounting screw
1
②
PCB 1
⑥
Wiring (For communication)
1
③
PCB mounting support
2
⑦
Wiring (For receiving) 1
④
Bracket (Sheet metal) 1
⑧
Installation manual 1
⑨
Parts set 1
Master/Slave setting when using
multiple remote controls
Up to two receivers or wired remote
controls can be installed on one
indoor unit group. In such occasion, it
is necessary to change the setting to
slave on either one.
To change the setting on the receiver,
refer to the instruction manual of the
receiver.
ONOFF
Default
settings
Switch
1
2
3
4
④
②
Drain pipe
Slide
Refrigerant pipe
③
⑨
⑩
③
①
②
Installation of
④
,
⑤
brackets (Sheet metal)
(Insert)
Cut off at 4 places.
Bracket (Sheet metal)
Bracket mounting
screw
PCB mounting support
Wiring
(Receiver)
hook
⑧
⑥
PCB
Wiring
(Communication)
⑦
4
Wireless remote controller
4
Wireless remote controller (continued)
Installation tips for the remote controller holder
Fix the remote controller holder using the screws supplied
with this product.
* Precautions for installing the holder
• Adjust the position so that it is upright.
• Ensure that the screw heads are not protruding.
• DO NOT attach the holder on plaster wall
How to insert batteries
1. Detach the back lid.
2. Insert the batteries. (two AAA batteries)
3. Reattach the back lid.
Setting to avoid mixed communication
1. Detach the back lid, and remove the batteries.
2. Cut off the switching wire in the battery compartment using nippers.
3. Insert the batteries, and attach the back lid.
Changing the remote controller setting
How to change the Auto Run setting
The Auto Run mode is not available on the building air conditioning and gas heat
pump series (excluding the cooling/heating free multi system).
When using the remote controller to operate those models, set the remote controller
to disable the Auto Run mode.
To disable the Auto Run mode, press the
ACL
switch while holding down the
MODE
button, or insert batteries while holding down the
MODE
button.
* Note: Once the batteries are removed, the setting is reset to the factory default.
When the batteries are removed, repeat the steps described above.
Indoor function settings
1. How to set indoor functions
1
Press the ON/OFF button to stop the unit.
2
Press the desired one of the buttons shown item 2. while holding down the
FUNCTION SETTING switch.
3
Use the selection buttons
▲
and
▼
to change the setting.
4
Press the SET button.
The buzzer on the remote control signal receiver beeps twice, and the LED
lamp flashes four times at two-second intervals.
For the shop series
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the indoor unit PCB from [000]
to [127] so as not to duplicate.
For the building air conditioning and gas heat pump series
Set the indoor unit and outdoor unit numbers by manually specifying the addresses.
Use the rotary SW1 and SW2 provided on the indoor unit PCB (printed circuit board) to set the indoor unit
numbers so that they are not duplicated.
Master/Slave setting when using multiple remote controller
Up to two receivers can be installed in one indoor unit group.
Wireless remote controller’s operable area
1. Standard reachable area of the signal
[Condition] Illuminance at the receiver: 300lux
(When no lighting is installed within 1m of the receiver in an ordinary office)
2. Correlation between illuminance at the
receiver and reachable area of the signal
in a plain view.
The drawing in the right shows the
correlation between the reachable area of
the signal and illuminance
at the receiver when the remote
controller is operated at 1m high
under the condition of ceiling
height of 2.4m.
When the illuminance becomes double,
the area is narrowed down to two thirds.
3. Installation tips when several receivers are installed close to one another.
Minimum distance between the indoor units which can avoid cross communication is 5m under the
condition of 300lux of illuminance at the receiver.
(When no lighting is installed within 1m of the receiver in an ordinary office )
Backup switch
A backup switch is provided on the receiver section of the panel
surface.
When operation from the wireless remote control unit is not possible
(due to flat batteries, a mislaid unit, a unit failure), you can use it as an
emergency means. You should operate this switch manually.
1. If pressed while the air conditioner is in a halt, it will cause the air
conditioner to start operation in the automatic mode (In case of
cooling only, it is in the cooling mode).
Wind speed: Hi fan, Temperature setting: 23°C, Louver: horizontal
2. If pressed while the air conditioner is in operation, it will stop the air conditioner
Cooling test run operation
• After safety confirmation, turn on the power.
•
Transmit a cooling operation command with the wireless remote control unit, while the backup switch
on the receiver is pressed.
• If the backup switch on the receiver is pressed during a test run, it will end the test run.
• If you cannot operate the unit properly during a test run, please check wiring by consulting with
inspection guides.
How to read the two-digit display
On the receiver of a wireless kit, a two-digit (7-segment) display is provided.
1. An indication will be displayed for one hour after power on.
2. An indication will be displayed for 3.5 seconds after transmitting a “STOP” command from the
wireless remote controller or the operation of the backup switch to stop the unit.
3. An indication appearing in (1) or (2) above will go off as soon as the unit starts operation.
4. When there are no error records to indicate, addresses of all the connected units are displayed.
5. When there are some error records remaining, the error records are displayed.
6. Error records can be cleared by transmitting a “STOP” command from the wireless remote
controller, while the backup button is pressed.
5
Receiver
5
Receiver (continued)
5
7
6
Wood screw
Holder for
remote controller
Ensure the correct
polarity when
inserting.
Auto Run setting
1
4
2
3
Indoor unit
SW2
[Master]
SW2
[Slave]
Remote controller line
(Non-polarized)
Reachable area of the signal
Ceiling surface
4m 3m 2m 1m 0 1m 2m 3m 4m
1m
1.4m
2.4m
Switch Setting Function
SW2
ON Master
OFF Slave
Te rminal block
Remote controller
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address (F)
Receiver
8
2. Setting details
The following functions can be set.
Button Number indicator Function setting
FAN SPEED
00 Fun speed setting : Standard
01 Fun speed setting : Setting 1 *
02 Fun speed setting : Setting 2 *
MODE
00 Room heating temperature adjustment : Disable
01 Room heating temperature adjustment : +1°C
02 Room heating temperature adjustment : +2°C
03 Room heating temperature adjustment : +3°C
FILTER
00 Filter sign display : OFF
01 Filter sign display : 180 hours
02 Filter sign display : 600 hours
03 Filter sign display : 1000 hours
04 Filter sign display : Operation stop after 1000 hours have elapsed
U/P
(Up/Down)
00 Anti draft setting : Disable
01 Anti draft setting : Enable
SILENT
00 Infrared sensor setting (Motion sensor setting) : Disable
01 Infrared sensor setting (Motion sensor setting) : Enable
HI POWER
00 Infrared sensor control (Motion sensor control) : Disable
01 Infrared sensor control (Motion sensor control) : Power control only
02 Infrared sensor control (Motion sensor control) : Auto OFF only
03 Infrared sensor control (Motion sensor control) : Power control + Auto OFF
ON TIMER
00 Cooling fan residual-period running : Disable
01 Cooling fan residual-period running : 0.5 hours
02 Cooling fan residual-period running : 2 hours
03 Cooling fan residual-period running : 6 hours
OFF TIMER
00 Heating fan residual-period running : Disable
01 Heating fan residual-period running : 0.5 hours
02 Heating fan residual-period running : 2 hours
03 Heating fan residual-period running : 6 hours
NIGHT
SETBACK
00 Remote control signal receiver LED : Brightness High
01 Remote control signal receiver LED : Brightness Low
02 Remote control signal receiver LED : OFF
* Refer to technical data.
Backup switch
Restrictions on the thickness and length of wire
(Maximum length is 600m.)
Standard Within 0.3 mm² × 100m
Within 0.5 mm² × 200m
Within 0.75mm² × 300m
Within 1.25mm² × 400m
Within 2.0 mm² × 600m
PJF012D506
1
Control multiple indoor units with one remote controller
Up to 16 indoor units can be connected.
1.
Connect the XY terminal with 2-core wire. As for the
size, refer to the note on the right.
2. For Packaged air conditioner series, set the indoor
unit address with SW2 on the indoor unit PCB from
[0] to [F] so as not to duplicate.
The receivable area of the
signal when the illuminance
at the receiver is 300lux
The receivable area of the
signal when the illuminance at
the receiver is 600lux
4m
4m
3m
3m
2m
2m
1m
1m
Cut