To change setting
Preparation before installation
1. Change the setting of switches on the accessory PCB.
2. When SW1 is turned to OFF position, change the wireless remote control setting.
Setting to avoid mixed communication of
For the method of changing the setting, refer to
④
Wireless remote control
.
*For the receivable area of the signal, refer to
⑤
Receiver
.
②
Preparation before installation (continued)
③
How to install the receiver
It is possible to install the receiver by replacing the corner lid on the panel.
①
Remove the inlet grille according to the installation manual of the panel.
②
Remove the corner lid at the refrigerant pipe side.
③
Loosen screws (2 pcs.) on the control box of the unit.
④
Slide the control lid in the arrow direction, and remove it.
Master/Slave setting when using
multiple remote controls
Up to two receivers or wired remote
controls can be installed on one
indoor unit group. In such occasion, it
is necessary to change the setting to
slave on either one.
To change the setting on the receiver,
refer to the instruction manual of the
receiver.