40
Before operation
3.3 Before operation
3.3.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. (For details of parameters, 
 Refer to Chapter 4 of the Instruction Manual (Applied)).
POINT
Only simple mode parameters are displayed by the initial setting of 
Pr. 160 Extended function display selection
. Set 
Pr.
160 Extended function display selection 
as required. (
Refer to page 37
 for parameter change)
Pr. 160 Description
9999
(initial value)
Parameters classified as simple mode can be displayed.
0
Both the parameters classified as simple mode and the parameters 
classified as extended mode can be displayed.
Parameter 
Number
Name Unit
Initial 
Value
Range Application
Reference
Page
0 Torque boost 0.1%
6%/4%/3/
2%∗
0 to 30%
Set when you want to increase a 
starting torque under V/F control,  
or when the motor with a load will 
not rotate, resulting in an alarm 
[OL] and a trip [OC1].
∗ Initial values differ according to the
inverter capacity. (0.75K or less/
1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
44
1 Maximum frequency 0.01Hz 120Hz 0 to 120Hz
Set when the maximum output 
frequency need to be limited.
45
2 Minimum frequency 0.01Hz 0Hz 0 to 120Hz
Set when the minimum output 
frequency need to be limited.
3 Base frequency 0.01Hz 60Hz 0 to 400Hz
Set when the rated motor 
frequency is 50Hz.
Check the motor rating plate.
43
4
Multi-speed setting 
(high speed)
0.01Hz 60Hz 0 to 400Hz
Set when changing the preset 
speed in the parameter with a 
terminal.
64
5
Multi-speed setting 
(middle speed)
0.01Hz 30Hz 0 to 400Hz
6
Multi-speed setting (low 
speed)
0.01Hz 10Hz 0 to 400Hz
7 Acceleration time 0.1s 5s/10s/15s∗ 0 to 3600s
Acceleration/deceleration time can 
be set.
∗ Initial values differ according to the
inverter capacity. (3.7K or less/
5.5K, 7.5K/11K, 15K)
46
8 Deceleration time 0.1s 5s/10s/15s∗ 0 to 3600s
9
Electronic thermal O/L 
relay
0.01A
Rated 
inverter 
current
0 to 500A
The inverter protects the motor 
from overheat.
Set the rated motor current.
41
79
Operation mode 
selection
10
0, 1, 2, 3, 4, 6, 
7
Select the start command location 
and frequency setting location.
47
125
Terminal 2 frequency 
setting gain frequency
0.01Hz 60Hz 0 to 400Hz
Frequency for the maximum value 
of the potentiometer (5V initial 
value) can be changed.
68
126
Terminal 4 frequency 
setting gain frequency
0.01Hz 60Hz 0 to 400Hz
Frequency for the maximum 
current input (20mA initial value) 
can be changed.
71
160
Extended function 
display selection
1 9999 0, 9999
Parameter which can be read from 
the operation panel and parameter 
unit can be restricted.
74