FR-D700
INSTRUCTION MANUAL (BASIC)
FR-D720-0.1K to 15K
FR-D740-0.4K to 15K
FR-D720S-0.1K to 2.2K
FR-D710W-0.1K to 0.75K
INVERTER
IB(NA)-0600365ENG-F(0910)MEE Printed in Japan Specifications subject to change without notice.
FR-D700 INVERTER INSTRUCTION MANUAL (BASIC)
F
700
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
1
2
3
4
5
6
MODEL
MODEL
CODE
1A2-P34
FR-D700
INSTRUCTION MANUAL (BASIC)
CONTENTS
PRODUCT CHECKING AND PARTS IDENTIFICATION ............................. 1
INSTALLATION AND WIRING ..................................................................... 2
2.1 Peripheral devices..................................................................................................... 3
2.2 Removal and reinstallation of the cover.................................................................... 4
2.3 Installation of the inverter and instructions ............................................................... 7
2.4 Wiring ........................................................................................................................ 9
2.5 When using the brake resistor (MRS type, MYS type, FR-ABR) ........................... 26
2.6 Power-OFF and magnetic contactor (MC).............................................................. 27
2.7 Precautions for use of the inverter .......................................................................... 28
2.8 Failsafe of the system which uses the inverter ....................................................... 30
DRIVE THE MOTOR ................................................................................... 31
3.1 Step of operation..................................................................................................... 31
3.2 Operation panel....................................................................................................... 32
3.3 Before operation...................................................................................................... 40
3.4 Start/stop from the operation panel (PU operation)................................................ 54
3.5 Make a start and stop with terminals (External operation) ..................................... 62
3.6 Parameter list .......................................................................................................... 72
TROUBLESHOOTING ................................................................................ 96
4.1 Reset method of protective function ....................................................................... 96
4.2 List of fault or alarm indications .............................................................................. 97
4.3 Causes and corrective actions................................................................................ 98
4.4 Correspondences between digital and actual characters..................................... 107
4.5 Check and clear of the faults history..................................................................... 108
4.6 Check first when you have a trouble..................................................................... 110
PRECAUTIONS FOR MAINTENANCE AND INSPECTION..................... 117
5.1 Inspection items .................................................................................................... 117
SPECIFICATIONS..................................................................................... 125
6.1 Rating .................................................................................................................... 125
6.2 Common specifications......................................................................................... 127
6.3 Outline dimension drawings.................................................................................. 128
APPENDIX................................................................................................. 131
Thank you for choosing this Mitsubishi Inverter.
This Instruction Manual (Basic) is intended for users who "just want to run the inverter".
If you are going to utilize functions and performance, refer to the Instruction Manual (Applied) [IB-0600366ENG]. The
Instruction Manual (Applied) is separately available from where you purchased the inverter or your Mitsubishi sales
representative.
1
2
3
4
5
6

Table of Contents

Questions and Answers

  • C
    Christopher AcostaAug 20, 2025
    How to unlock password on Mitsubishi Inverter?
    • K
      Kimberly SpencerAug 20, 2025
      To unlock a password-locked Mitsubishi Inverter, enter the password in Pr. 297 Password lock/unlock before operating.
  • A
    Amy GrossAug 22, 2025
    How to unlock operation panel on Mitsubishi FR-D720-5.5K Inverter?
    • J
      Jason HarrisAug 22, 2025
      To release the operation panel lock on the Mitsubishi Inverter, press the lock button for 2 seconds.
  • J
    Joseph SmithAug 25, 2025
    What to do if Mitsubishi Inverter shows overload trip error?
    • D
      donna85Aug 25, 2025
      If the temperature of the output transistor element exceeds the protection level when a current not less than the rated inverter current flows (200% or less), the electronic thermal relay activates, stopping the Mitsubishi Inverter output. To resolve this, try increasing the acceleration/deceleration time or adjusting the torque boost setting.
  • T
    Tracy Gordon PhDAug 26, 2025
    Why is my Mitsubishi FR-D720-5.5K showing an undervoltage error?
    • R
      Richard HayesAug 27, 2025
      If the Mitsubishi Inverter's power supply voltage decreases, the control circuit won't function normally. Check the power supply system equipment, including the power supply itself, to resolve this issue.
  • R
    rayjamesAug 28, 2025
    How to fix a write disable error on a Mitsubishi FR-D720-5.5K Inverter?
    • M
      Matthew GloverAug 28, 2025
      A write disable error on your Mitsubishi Inverter can occur due to several reasons. First, it could be because you're trying to change a parameter when Pr. 77 (Parameter write selection) is set to disable writing. Check the setting of Pr. 77 to resolve this. Second, the frequency jump setting range might be overlapping; review the settings of Pr. 31 to Pr. 36 (frequency jump). Finally, the PU and inverter may not be communicating correctly; check their connection.
  • J
    Jaime GarciaAug 30, 2025
    What causes a motor overload trip on a Mitsubishi FR-D720-5.5K Inverter?
    • R
      Rick FaulknerAug 30, 2025
      The Mitsubishi Inverter's electronic thermal relay function detects motor overheat, which can be caused by overload or reduced cooling during constant-speed operation. To resolve this, reduce the load weight.
  • K
    Kelly WoodSep 1, 2025
    What does stall prevention (overcurrent) mean on a Mitsubishi Inverter?
    • J
      Juan BoydSep 1, 2025
      During acceleration, if the Mitsubishi Inverter's output current exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), the function stops the frequency increase until the overload current decreases. This prevents the inverter from an overcurrent trip.
  • A
    angela86Sep 3, 2025
    What to do if Mitsubishi Inverter shows input phase loss?
    • S
      Shane SpearsSep 3, 2025
      The Mitsubishi Inverter trips if Pr. 872 Input phase loss protection selection is set to valid (=1) and one phase of the three-phase power input is lost. Ensure the cables are properly wired and repair any breaks in the cable.
  • K
    Kevin MillerSep 5, 2025
    Why does my Mitsubishi Inverter show a write error during operation?
    • L
      Laura RogersSep 5, 2025
      A write error during operation on a Mitsubishi Inverter happens when parameter writing is performed during operation with a value other than "2" set in Pr. 77, and the STF (STR) is ON. To solve this, set "2" in Pr. 77 or stop the operation before making parameter settings.
  • A
    Amanda BautistaSep 7, 2025
    How to troubleshoot output phase loss on a Mitsubishi FR-D720-5.5K?
    • R
      rossrobertaSep 7, 2025
      Output phase loss on a Mitsubishi Inverter occurs if one of the three phases (U, V, W) on the inverter's output side is lost during operation. Ensure the cables are properly wired.

Summary

INSTALLATION AND WIRING

Wiring

Details on terminal connections, main circuit, control circuit, and safety stop wiring.

Precautions for use of the inverter

Important safety and operational guidelines to prevent damage or malfunction.

DRIVE THE MOTOR

Operation panel

Details on the functions and indicators of the inverter's operation panel.

TROUBLESHOOTING

Reset method of protective function

Procedures for resetting protective functions after a fault occurs.

List of fault or alarm indications

Table of operation panel indications for faults, warnings, and alarms.

Causes and corrective actions

Detailed troubleshooting guide with possible causes and solutions for errors.

Check first when you have a trouble

Step-by-step guide to diagnose common operational issues.

PRECAUTIONS FOR MAINTENANCE AND INSPECTION

Mitsubishi FR-D720-5.5K Specifications

General IconGeneral
ModelFR-D720-5.5K
SeriesFR-D700
CategoryInverter
Rated Output Power5.5 kW
Applicable Motor Capacity5.5kW
Input Frequency50/60 Hz
Output Frequency0.5-400 Hz
Enclosure RatingIP20
Horsepower7.5 HP
Overload Capacity150% for 1 minute
Control MethodV/f control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overload, short circuit, ground fault, overheating
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity95% RH or less (non-condensing)
AltitudeUp to 1000 m
Built-in FunctionsPID control
Cooling MethodForced air cooling