8
Installation of the inverter and instructions
Install the inverter under the following conditions.
The inverter consists of precision mechanical and electronic parts. Never install or handle it in any of the following
conditions as doing so could cause an operation fault or failure.
Surrounding air temperature and humidity
Measurement
position
Measurement
position
Inverter
5cm
5cm
5cm
Clearances (side)
1cm
or more
*
Inverter
Clearances (front)
10cm or more
10cm or more
1cm
or more*
1cm
or more*
* 5cm or more for the 5.5K
or more
Leave enough clearances and
take cooling measures.
Humidity: 90% RH maximum
Temperature: -10 C to +50 C
-10 C to +40 C for totally
-enclosed structure feature
* When using the inverters at the surrounding air
temperature of 40 C or less, the inverters can be
installed without any clearance between them (0cm
clearance).
When surrounding air temperature exceeds 40 C,
clearances between the inverters should be 1cm or
more (5cm or more for the 5.5K or more).
Direct sunlight
High temperature,
high humidity
Oil mist, flammable
gas, corrosive gas,
fluff, dust, etc.
Horizontal placement
Transportation by
holding front cover
or setting dial
When mounted inside
enclosure
Mounting to
combustible material
Vibration
(5.9m/s
2
or more at
10 to 55Hz (directions
of X, Y, Z axes))