75
DRIVE THE MOTOR
3
Parameter list
Parameter List
3.6.3 Parameter list
indicates simple mode parameters.
......V/F control
......General-purpose magnetic flux vector control
(Parameters without any mark are valid for all control.)
"" indicates enabled and "x" indicates disabled of "parameter copy", "parameter clear", and "all parameter clear".
"" indicates a communication parameter which is not cleared by parameter clear (all clear) from RS-485 communication.
(For more information on RS-485 communication,
refer to Chapter 4 of the Instruction Manual (Applied).)
Function
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
Copy
Parameter
Clear
All Parameter
Clear
Related
Parameter
Manual torque
boost
0
Torque boost
0.1%
6/4/3/
2%
0 to 30%
Set the output voltage at 0Hz as %.
* Initial value depends on the inverter capacity.
(0.75K or more/1.5K to 3.7K/5.5K, 7.5K/11K,
15K)

46
Second torque
boost
0.1% 9999
0 to 30% Torque boost when the RT signal is on.

9999 Without second torque boost
Maximum/minimum
frequency
1
Maximum
frequency
0.01Hz 120Hz 0 to 120Hz Upper limit of the output frequency. 
2
Minimum
frequency
0.01Hz 0Hz 0 to 120Hz Lower limit of the output frequency. 
18
High speed
maximum
frequency
0.01Hz 120Hz
120 to
400Hz
Set when performing the operation at
120Hz or more.

Base frequency, voltage
3
Base frequency
0.01Hz 60Hz 0 to 400Hz
Rated motor frequency.
(50Hz/60Hz)

19
Base frequency
voltage
0.1V 9999
0 to 1,000V Base voltage.

8888
95% of power supply voltage
(95% of doubled power supply voltage for
single-phase 100V power input model.)
9999
Same as power supply voltage
(Twice the amount of the power supply
voltage for single-phase 100V power input
model.)
47
Second V/F (base
frequency)
0.01Hz 9999
0 to 400Hz Base frequency when the RT signal is ON.

9999 Second V/F invalid
Multi-speed setting
operation
4
Multi-speed setting
(high speed)
0.01Hz 60Hz 0 to 400Hz Frequency when RH turns ON. 
5
Multi-speed setting
(middle speed)
0.01Hz 30Hz 0 to 400Hz Frequency when RM turns ON. 
6
Multi-speed setting
(low speed)
0.01Hz 10Hz 0 to 400Hz Frequency when RL turns ON. 
24
to
27
Multi-speed setting
(4 speed to 7 speed)
0.01Hz 9999
0 to 400Hz
9999
Frequency from 4 speed to 15 speed can
be set according to the combination of the
RH, RM, RL and REX signals.
9999: not selected

232
to
239
Multi-speed setting
(8 speed to 15
speed)
0.01Hz 9999
0 to 400Hz,
9999

V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC
V/F
V/F
V/F
V/F
V/F
V/F

Table of Contents