2
Product Checking
1 Product Checking
(1) Unpack the option unit, and ensure that the product received is as you 
ordered and it is intact.
(2) Make sure that the package includes all accessories.
*The terminal cover for the 200V class 15K or less is provided on the terminal block.
2 Installation
(1) Install according to the environment conditions on page 5.
(2) Fully take caution not to make the ambient temperature higher than the 
permissible value (-10°C to +50°C). In addition, as the reactor itself 
generates heat, leave sufficient clearances around it. (Independently of 
the installation direction of the reactor 10 cm or more for the above and 
below, 5 cm or more for the right and left)
AC reactor
 (FR- HAL)...................... 1
Terminal block cover .......1
(15K or less for the 200V 
class, 55K or less for the 
400V class) *
Instruction manual ..........1
AC REACTOR
FR-HAL-        K
FR-HAL- H         K
XXXXXXXXXXXX
SERIAL
MITSUBISHI ELECTRIC CORP.
MODEL
Applied motor capacity (kW)
Applied Power Supply VoltageSymbol
None
200V class
MITSUBISHI
H
400V class
5cm or more
5cm or more
5cm or more
10cm or more
5cm or more