5
Specifications
ENGLISH
5 Specifications
*1 The power factor is calculated on the assumption that the power impedance is 1%. The
value changes according to the power supply capacity and power impedance. The load is
calculated using the fundamental current specified in JEM-TR201 as 100%.
For a motor of less than 0.4kW, the power factor improving effect will be slightly lower.
*2 2.9m/s
2
or less for the H185K or more
FR-HAL-H55K
55K M8 60-8 60
FR-H
AL-H75K
75K M10 60-10 60
FR-H
AL-H110K
90K M12 60-12 60
FR-H
AL-H110K
110K M12 80-12 80
FR-H
AL-H185K
132K M12 100-12 100
FR-H
AL-H185K
160K M12 150-12 125
FR-H
AL-H185K
185K M12 150-12 150
FR-H
AL-H280K
220K M12 100-12 2 × 100
FR-H
AL-H280K
250K M12 100-12 2 × 100
FR-H
AL-H280K
280K M12 150-12 2 × 125
FR-H
AL-H355K
315K M16 150-16 2 × 150
FR-H
AL-H355K
355K M16 200-16 2 × 200
FR-H
AL-H560K
400K M12 C2-200 2 × 200
FR-H
AL-H560K
450K M12 C2-250 2 × 250
FR-H
AL-H560K
500K M12 C2-250 2 × 250
FR-H
AL-H560K
560K M12 C2-200 3 × 200
Power Factor Improving Effect *1 Power supply power factor 88% or more (at 100% load)
Power specifications
200V class Three-phase AC 200 to 240V 50Hz/60Hz
400V class
55K or less
Three-phase AC 380 to 480V
50Hz/60Hz
75K or more
Three-phase AC 380 to 500V
50Hz/60Hz
Envi-
ron-
ment
Ambient temperature -10°C to + 50°C (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Storage temperature -20°C to + 65°C (non-freezing)
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust
and dirt)
Altitude/vibration
Max.1000m above sea level 5.9m/s
2
or less *2
Type
Applicable
Inverter Capacity
Terminal
Screw Size
Crimping
Terminal
HIV Cable Size
(mm
2
)