123
"LINK PARA.
ERROR"
47
473*
Continue
[When using
MELSECNET/10]
(1) The contents of the
network parameters
for the first link unit,
written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the first link unit
have not been written.
(3) The setting for the
total number of
stations is 0.
(1) Write the
parameters
again and
check.
(2) Check the
station number
settings.
(3) Persistent
error
occurrence
may indicate a
hardware fault.
Consult your
nearest
Mitsubishi
representative,
explaining the
nature of the
problem.
474*
[When using
MELSECNET/10]
(1) The contents of the
network parameters
for the second link
unit, written from a
peripheral device,
differ from the actual
network system.
(2) The link parameters
for the second link
unit have not been
written.
(3) The setting for the
total number of
stations is 0.
(1) Write the
parameters
again and
check.
(2) Check the
station number
settings.
(3) Persistent
error
occurrence
may indicate a
hardware fault.
Consult your
nearest
Mitsubishi
representative,
explaining the
nature of the
problem.
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A A1SCPUC24-R2 and is the answer not in the manual?

Mitsubishi MELSEC-A A1SCPUC24-R2 Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A A1SCPUC24-R2
CategoryController
LanguageEnglish

Related product manuals