Mitsubishi MSH-30RV - Additional Refrigerant Charge

Mitsubishi MSH-30RV
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Model
MSH-18RV -
E1
MUH-18RV - E1
MUH-18RV - E2
Refrigerant piping length (one way)
Outdoor unit precharged
1,650
15m
400
7m
0
10m
150
ADDITIONAL REFRIGERANT CHARGE(R22 : g)
Calculation : Xg=50g/m (Refrigerant piping length (m)–7)
Model
MSH-24RV -
E1
MUH-24RV - E1
Refrigerant piping length (one way)
Outdoor unit precharged
2,400
15m
520
7m
0
10m
195
Calculation : Xg=65g/m (Refrigerant piping length (m)–7)
Outdoor unit
precharged
0
195
520
Refrigerant piping length (one way)
15m10m7m
Model
MSH-30RV -
2,300
E1
20m 25m
30m
845 14951170
MUH-30RV -
E1
Calculation : Xg=65g/mo(Refrigerant piping length(m)-7)
OB272-1.qxp 02.1.26 1:22 PM Page 19