13. Removing the reactor (DCL)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box (See photo 5)
(4) Remove 4 screws for reactor (4 x 10) to remove the reac-
tor. (See Figure 1)
14. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 5)
(4) Remove the valve bed. (Refer to procedure 8 (4))
(5) Remove the cover panel (front). (Refer to procedure 8(5))
(6) Remove the cover panel (rear) (Refer to procedure 8(6))
(7) Remove the side panel (R). (Refer to procedure 8 (7))
(8) Remove front panel fixing screws, 5 (5x12) and 2 (4 x 10)
and remove the front panel. (See Photo 4)
(9) Remove 3 separator fixing screws (4 × 10) and remove the
separator. (See Figure 3)
(10)
Recover refrigerant.
(11)
Remove the 3 compressor fixing nuts using spanner or
adjustable wrench.
(12)
Remove the welded pipe of motor for compressor inlet and
outlet and then remove the compressor.
Note: Recover refrigerant without spreading it in the air.
Reactor
Electrical parts box
Figure 2
Screws
for reactor
Connectors of
reactor
Bottom plate of
electrical parts box
Photo 13
Photo 14
Figure 3
Separator
fixing
screws
Separator
fixing screw
Valve bed
Front cover panel
fixing screws
Valve bed
fixing screw
Rear cover panel
fixing screws
Valve bed
fixing screws
Right side
panel
Compressor
(MC)
Separator
fixing screw
Compressor
fixing nut
Separator
Accumulator
Accumulator
leg
Accumulator leg
fixing screws