158
OPERATING PROCEDURE PHOTOS
15. Removing the accumulator
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 5)
(4)
Remove the valve bed. (See procedure 8 (4))
(5) Remove the cover panel (front). (Refer to procedure 8(5))
(6) Remove the cover panel (rear) (Refer to procedure 8(6))
(7) Remove the side panel (R). (Refer to procedure 8 (7))
(8) Recover refrigerant.
(9) Remove 2 welded pipes of accumulator inlet and outlet.
(10)
Remove 2 accumulator leg fixing screws (4 × 10). (See
Photo 16)
Note: Recover refrigerant without spreading it in the air.
Accumulator
Photo 16
Inlet
Outlet
Accumulator
Accumulator leg
Accumulator leg fixing
screws