BRANCH BOX: PAC-MKA50BC PAC-MKA51BC PAC-MKA30BC PAC-MKA31BC
1
2
3
4
5
M
Blue
Yellow
Orange
Red
White
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50 to 86°F [10 to 30:])
Disconnect the connector then measure the resistance with a tester.
(
Winding temperature 68°F [20
:
]
)
Thermistor (TH-A–E)
<Gas pipe>
Normal
4.3 to 9.6k"
Abnormal
Open or short
Normal
Red - White
Red - Orange
Red - Yellow
Red - Blue
Abnormal
46 ± 4"
Linear expansion valve
( LEV-A–E )
Open or short
OCH573C