135
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678 1 2 3 4 5 6 7 8
220 00111011
IC6 TH23 (Gas)
−99.9–999.9 (
_
F)
Display detected data of
indoor unit thermistor
221 10111011
IC7 TH23 (Gas)
222 01111011
IC8 TH23 (Gas)
223 11111011
IC6 TH22 (liquid)
224 00000111
IC7 TH22 (liquid)
225 10000111
IC8 TH22(liquid)
226 01000111
IC6 TH21 (intake)
227 11000111
IC7 TH21 (intake)
228 00100111
IC8 TH21 (intake)
229 10100111 IC6 SC/SH
−99.9–999.9 (degree)
during heating: subcool (SC)/during cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data
230 01100111 IC7 SC/SH
231 11100111 IC8 SC/SH
232 00010111
Target indoor SC/SH
(IC6)
SCm/SHm (0.0–20.0) (degree)
Display of all control target
data
233 10010111
Target indoor SC/SH
(IC7)
234 01010111
Target indoor SC/SH
(IC8)
235 11010111
IC6 LEV opening pulse
abnormality delay
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality delay
236 00110111
IC7 LEV opening pulse
abnormality delay
237 10110111
IC8 LEV opening pulse
abnormality delay
238 01110111
IC6 SC/SH at time of
abnormality delay
−99.9–999.9 (degree)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
delay
239 11110111
IC7 SC/SH at time of
abnormality delay
240 00001111
IC8 SC/SH at time of
abnormality delay
241 10001111
IC6 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality
242 01001111
IC7EV opening pulse
at time of abnormality
243 11001111
IC8 LEV opening pulse
at time of abnormality
244 00101111
IC6 SC/SH at time of
abnormality
−99.9–999.9 (degree)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
delay
245 10101111
IC7 SC/SH at time of
abnormality
246 01101111
IC8 SC/SH at time of
abnormality
250 01011111 IC9 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
251 11011111
IC10 LEV opening pulse
252 00111111
IC11 LEV opening pulse
253 10111111
IC12 LEV opening pulse
OCH573C