EasyManua.ls Logo

Mitsubishi MXZ-8C60NA-U1 - Page 150

Mitsubishi MXZ-8C60NA-U1
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
150
OPERATING PROCEDURE
PHOTOS
9. Removing bypass valve coil (SV1) and bypass valve
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (Refer to procedure 8 (5))
(4) Remove the cover panel (rear). (Refer to procedure 8 (6))
(5) Remove the side panel (R). (Refer to procedure 8 (7))
(6) Remove the bypass valve coil fixing screw (M4 × 6).
(7) Remove the bypass valve coil by sliding the coil upward.
(8) Disconnect the connector SV1 (gray) on the multi controller
circuit board in the electrical parts box.
(9) Remove the electrical parts box. (See Photo 4)
(10)
Recover refrigerant.
(11)
Remove the welded part of bypass valve.
Refer to the notes below.
Photo 10
10. Removing the high pressure switch (63H) and high pres-
sure sensor (63HS)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (Refer to procedure 8 (5))
(4) Remove the cover panel (rear). (Refer to procedure 8 (6))
(5) Remove the side panel (R). (Refer to procedure 8 (7))
(6) Pull out the lead wire of high pressure switch and high pres-
sure sensor.
(7) Remove the electrical parts box. (See Photo 4)
(8) Recover refrigerant.
(9) Remove the welded part of high pressure switch and high
pressure sensor.
Refer to the notes below.
11. Removing the low pressure sensor (63LS)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (Refer to procedure 8 (5))
(4) Remove the cover panel (rear). (Refer to procedure 8 (6))
(5) Remove the side panel (R). (Refer to procedure 8 (7))
(6) Disconnect the connector 63LS (blue) on the multi controller
circuit board in the electrical parts box.
(7) Remove the electrical parts box. (See Photo 4)
(8) Recover refrigerant.
(9) Remove the welded part of low pressure sensor.
Refer to the notes below.
12. Removing electrical expansion valve (LEV-A, LEV-B)
(1) Remove the service panel. (See Figure 1)
(2) Remove the top panel. (See Figure 1)
(3) Remove the cover panel (front). (Refer to procedure 8 (5))
(4) Remove the cover panel (rear). (Refer to procedure 8 (6))
(5) Remove the side panel (R). (Refer to procedure 8 (7))
(6)
Remove the electrical expansion valve coil. (See Photo 10,11)
(7) Remove the electrical parts box. (See Photo 4)
(8) Recover refrigerant.
(9) Remove the welded part of electrical expansion valve.
Refer to the notes on the right.
Photo 11
Low pressure
sensor (63LS)
Electronic expansion
valve coil (LEV-A)
Electronic
expansion valve
High pressure
sensor (63HS)
High pressure
switch (63H)
Low pressure
sensor (63LS)
Bypass valve
coil fixing screw
Electronic expansion
valve coil (LEV-B)
Bypass valve
coil (SV1)
Bypass valve
Electronic
expansion
valve
Notes:
1. Recover refrigerant without spreading it in the air.
2. The welded part can be removed easily by removing
the side panel (R).
3. When installing the following parts, cover it with a
wet cloth to prevent it from heating as the tempera-
ture below, then braze the pipes so that the inside of
pipes are not oxidized;
Bypass valve (procedure 9), 248-F [120°C] or more
High pressure switch and high pressure sensor
(procedure 10), 212-F [100°C] or more
Low pressure sensor (procedure 11), 212-F [100°C]
or more
LEV (procedure 12), 248-F [120°C] or more
OCH573C

Related product manuals