31
• Name, Symbol, and the Maximum Units for Connection
Permissible LengthProhibited items
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wring
together.
: Group 1
: Group 3
: Group 5
: Shielded Wire
: Sub Remote Controller
( ): Address
M1 M2 S
TB7
IC
(51)
M1 M2 1 2S
TB5 TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB15
MA
(01)
IC
M1 M2 S
TB5
(03)
IC
M1 M2 S
TB5
(02)
IC
M1 M2 S
TB5
(04)
IC
M1 M2 S
TB5
(05)
IC
M1 M2 S
TB5
(07)
IC
M1 M2 S
TB5
(06)
MA
MA
MA
OC
M1 M2 S
TB7
(53)
OC
S
Power Supply
Unit
S
G-50A
AB
AB
AB
M1M2
M1M2
AB
M1M2 S
TB3
M1M2 S
TB3
Longest length via outdoor unit (M-NET cable): L1+L2+L3+L4 and L1+L2+L6+L7 500 m (1.25 A or more)
Longest transmission cable length (M-NET cable): L
1
and L
3
+L
4
and L
6
and L
2
+L
6
and L
7
200 m (1.25 A or more)
Remote controller cable length:
m1
and
m1
+
m2
+
m3
and
m1
+
m2
+
m3
+
m4
200 m (0.3 to 1.25 A)