3-2. UNIT SPECIFICATIONS
(2) Method for identifying MULTI-S model
(1) Outdoor Unit
Indoor unit < When using Model 80 >
Outdoor unit <When using model 125 >
P L F Y - P 80 V AM - E PU M Y - P 125 Y H M A - BS
PAC type
AM
BM
CM
KM
M
KM
LMD
Frequency
conversion
controller
Refrigerant
R407C/R22
R410A
commonness
Refrigerant
R410A
NEW frequency converter
one-to-many air conditioners
(flexible design type)
Indicates equivalent
to Cooling capacity
Indicates equivalent
to Cooling capacity
Power supply
V: Single phase
220-230-240V 50Hz
220V 60Hz
Power supply
Y: 3-phase
380-400-415V 50Hz
L : Ceiling cassette
K : Wall-mounted type
E : Hidden skylight type
C : Ceiling suspended type
M : Ceiling cassette type
F : Floor standing type
}
M-NET
control
Outdoor unit
model type
Sub-number
M-NET control
Sub-number
Frequency
conversion
controller
Outdoor unit
MULTI-S
(k cal / h)
(k cal / h)
Salt proof type
Service Ref.
PUMY-P100YHM
PUMY-P100YHM
1
PUMY-P100YHMA(-BS)
Capacity
Cooling (kW)
Heating (kW)
11.2
12.5
1.9
PUMY-P125YHM
PUMY-P125YHM1
PUMY-P125YHMA (-BS)
14.0
16.0
2.4
PUMY-P140YHM
PUMY-P140YHM1
PUMY-P140YHMA (-BS)
16.0
18.0
2.9Motor for compressor (kW)
Cooling / Heating capacity indicates the maximum value at operation under the following condition.
w. Cooling Indoor : D.B. 27°C / W.B. 19.0°C
Outdoor : D.B. 35°C
Heating Indoor : D.B. 20°C
Outdoor : D.B. 7°C / W.B. 6°C
(3) Operating temperature range
Notes D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
w1. 10~46°C DB : In case of connecting PKFY-P20/P25 type indoor unit.
Cooling
W
.B. 15~24C
D.B. -5~46C
+1
Heating
D.B. 15~27C
W.B. -15~15C
Indoor-side intake air temperature
Outdoor-side intake air temperature
In case of connecting fresh air type indoor unit (Only PUMY-P·YHM1/YHMA can connect Fresh air type indoor unit.)
air type indoor
Capacity of Fresh
Cooling
Heating
Indoor-side and Outdoor-side
P80
D.B.21~43
+
2
W.B.15.5~35
D.B.-10~20
+
3
intake air temperature
P140
D.B.21~43
+
2
W.B.15.5~35
D.B.-5~20
+
3
+
2.Thermo-off (FAN-mode) automatically starts if the outdoor temp. is lower than 21D.B..
+
3.Thermo-off (FAN-mode) automatically starts if the outdoor temp. is higher than 20D.B..