91
11
EASY MAINTENANCE FUNCTION
11-1. SMOOTH MAINTENANCE
11-1-1. PAR-30MAA/PAR-31MAA
Maintenancedata,suchastheindoor/outdoorunit’sheatexchangertemperatureandcompressoroperationcurrentcanbe
displayedwith“Smoothmaintenance”.
This cannot be executed during test operation.
Depending on the combination with the outdoor unit, this may not be supported by some models.
F1 F2 F3 F4
Check menu
Cursor
Service menu:
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Smooth maintenance
Begin:
Smooth maintenance
Exit:
Ref.address
Stable mode
Cursor
−
Address
+
Ref.address
Stable mode
Stabilization→Collecting
Cool / Heat/ Normal
Cool / Heat/ Normal
Smooth maintenance
Return:
Smooth maintenance
Return:
Smooth maintenance
Return:
Page
Page
Page
COMP. current
COMP. run time
COMP. On / Off
COMP. frequency
A
Hz
Hr
times
Hr
Ref. address
Cool
Ref.address
Cool
Ref.address
Cool
Sub cool
OU TH4 temp.
OU TH6 temp.
OU TH7 temp.
IU air temp.
IU HEX temp.
IU filter time
Select"Smoothmaintenance"withthe F1 or F2 button,andpressthe
button.
Select"Check"withthe F1
or F2 button,andpressthe button.
Select"Service"fromtheMainmenu,andpressthe
button.
Seteachitem.
Selecttheitemtobechangedwiththe
F1
or
F2
button.
Selecttherequiredsettingwiththe
F3
or
F4
button.
■
<Ref.address>setting[0]to[15]
■
<Stablemode>setting[Cool]/[Heat]/[Normal]
Pressthe
button,Fixedoperationwillstart.
Note:Stablemodewilltakeapprox.20minutes.
Theoperationdatawillappear.
TheCompressor-Accumulatedoperating(COMP.run)timeis10-hourunit,
andtheCompressor-Numberofoperationtimes(COMP.ON/OFF)isa100-
timeunit(fractionsdiscarded).
Navigating through the screens
•TogobacktotheMainmenu..........
button
•Toreturntothepreviousscreen.......
button