96
3103
Although the number of modules has
been set to one or greater number in
the Ethernet module count
parameter setting, the number of
actually mounted module is zero.
The start I/O No. of the Ethernet
network parameter differs from the I/
O No. of the actually mounted
module.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA
AJ71QE71 does not exist in the
position of I/O number set by the
parameter.
I/O number designation is
overlapping.
Numbers of the network parameter
and loaded AJ71QE71 are different.
Ethernet (parameter + dedicated
instruction) is set to more than five.
QnA
3104
The Ethernet and MELSECNET/10
use the same network number.
The network number, station number
or group number set in the network
parameter is out of range.
The specified I/O number is outside
the range of the used CPU module.
The Ethernet-specific parameter
setting is not normal.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA
3105
The contents of the Ethernet parameter
are incorrect.
Write after correcting parameters. QnA
3107
The CC-Link parameter setting is
incorrect.
The set mode is not allowed for the
version of the mounted CC-Link
module.
Check the parameter setting. QnA