3.1.2 Installation instructions for EMC Directive 
The programmable controller is open equipment and must be installed within a 
control cabinet for use.* This not only ensures safety but also ensues effective 
shielding of programmable controller-generated electromagnetic noise. 
* : Also, each network remote station needs to be installed inside the control 
panel. 
However, the waterproof type remote station can be installed outside the 
control panel. 
(1) Control cabinet 
(a) Use a conductive control cabinet. 
(b) When attaching the control cabinet's top plate or base plate, mask 
painting and weld so that good surface contact can be made between 
the cabinet and plate. 
(c) To ensure good electrical contact with the control cabinet, mask the paint 
on the installation bolts of the inner plate in the control cabinet so that 
contact between surfaces can be ensured over the widest possible area. 
(d) Earth the control cabinet with a thick wire so that a low impedance 
connection to ground can be ensured even at high frequencies. 
(e) Holes made in the control cabinet must be 10 cm (3.94 in.) diameter or 
less. If the holes are 10 cm (3.94 in.) or larger, radio frequency noise 
may be emitted. 
(f)  Lock the control panel so that only those who are trained and have 
acquiredenough knowledge of electric facilities can open the control 
panel. 
(2) Connection of power and earth wires 
Earthing and power supply wires for the programmable controller system 
must be connected as described below. 
(a) Provide an earthing point near the power supply module. Earth the 
power supply's LG and FG terminals (LG: Line Ground, FG: Frame 
Ground) with the thickest and shortest wire possible. (The wire length 
must be 30 cm (11.81 in.) or shorter.) The LG and FG terminals function 
is to pass the noise generated in the programmable controller system to 
the ground, so an impedance that is as low as possible must be ensured. 
In addition, make sure to wire the ground cable short as the wires are 
used to relieve the noise, the wire itself carries large noise content and 
thus short wiring means that the wire is prevented from acting as an 
antenna. 
(b) The earth wire led from the earthing point must be twisted with the power 
supply wires. By twisting with the earthing wire, noise flowing from the 
power supply wires can be relieved to the earthing. However, if a filter is 
installed on the power supply wires, the wires and the earthing wire may 