66
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
1000
Runaway or failure of CPU module or
failure of main CPU
Malfunctioning due to noise or other
reason
Hardware fault
Take noise reduction measures.
Reset the CPU module and RUN it
again.If the same error is displayed
again, this suggests a CPU module
hardware fault.(Contact your local
Mitsubishi representative.)
QnA
1010
Entire program was executed without
the execution of an END instruction.
When the END instruction is
executed it is read as another
instruction code, e.g. due to noise.
The END instruction has been
changed to another instruction code
somehow.
Take noise reduction measures.
Reset the CPU module and RUN it
again. If the same error is displayed
again, this suggests a CPU module
hardware fault. (Contact your local
Mitsubishi representative.)
QnA