7
5.2 External wiring
(1) For Q62DAN and Q64DAN
(a) For voltage output
1 k
1 M
D/A
conversion
V+
COM
*1 *2
Motor drive module, etc.
GND
+24 V
A.G
+15 V
--15V
A.G
DC/DC
converter
24V
24G
FG
24 V DC
Filter
to
(b) For current output
0
600
D/A
conversion
I+
COM
*1 *2
Motor drive module, etc.
GND
+24V
A.G
+15V
–15V
A.G
DC/DC
converter
24V
24G
FG
24 V DC
Filter
to
*1 Use a twisted two core shielded wire for the power wire.
*2 If there is noise or ripples in the external wiring, connect a 0.1 to
0.47
F25V condenser between the V+/I+ terminal and COM.