Loading...
9
5.3 Switch setting for intelligent functional module
The settings for the intelligent function module are performed using the I/O
allocation settings for the GX Developer. When the intelligent function module
switches are not set, the default value for switches 1 to 5 is 0.
Setting item
Analog output range
Output range
setting value
4 to 20 mA 0H*
1
Switch 1
Output range setting
(CH1 to CH4)
H
CH4CH3CH2CH1
0 to 20 mA 1H
1 to 5 V 2H
0 to 5 V 3H
– 10 to 10 V 4H
User range setting FH
Switch 2
Output range setting
(CH5 to CH8)
H
CH8CH7CH6CH5
For Q62DAN and Q64DAN
H
CH4CH3CH2CH1
HOLD/CLEAR function setting
0
H
: CLEAR
1 to F
H
(numeric value other than 0
H
)*
: HOLD
Switch 3
For Q68DAVN and Q68DAIN
CH8CH7CH6CH5CH4CH3CH2CH1
b7 b6 b5 b4 b3 b2 b1 b0b8
0
b15
0to
HOLD/CLEAR function setting
0 : CLEAR
1 : HOLD
Switch 4
H
00
H
01 to FF
H
(numeric
value other than 00
H
)*
: Normal mode (non-synchronized)
: Synchronized output mode
0
H
1 to F
H
(numeric
value other than 0
H
)*
: Normal mode (D/A conversion processing)
: Offset/gain setting mode
0
H
1 to F
H
(numeric
value other than 0
H
)*
: Normal resolution mode
: High resolution mode
Switch 5 0 : Fixed
* Setting any value within the setting range will provide the same operation.
When the setting range is 1 to F
H
, set 1 for example.