8 - 18                     8 - 18
MELSEC-Q
8   TROUBLESHOOTING
C
No
Value of SW47
Value 3: No host send area
Value 4: Abnormal parameters detected
Value 5: Parameters not received
<Troubleshooting>
Check the contents of 
the common parameters 
and station inherent
parameters.
Value 0: 
The host 
transmitting 
normally
<Troubleshooting>
Checks the contents of each 
parameter that has been set 
in the refresh parameters
and remote I/O station that
have been set by the CPU
of the remote master station.
Yes
Normal communication
Is the 
send and receive 
data within the system 
specifications?
    If SW47=3, consider the following as a possible cause.
    Only the station number has been set in the common parameters and there is no link device allocation.
Is the send/
receive data according
 to system 
specifications?
No
<Troubleshooting>
Checks the contents of each
parameter that has been set
in the refresh parameters
and remote I/O station that
have been set by the CPU
of the remote master station.
Yes
Is the 
"RUN" LED of the 
applicable station 
lit?
Takes action according to 
the contents of SW47 and 
the error code contents that 
have been stored in SW48.
<Troubleshooting>
Yes
Is the 
power supplied to the 
power source 
module?
Yes
Yes
Execute offline tests.
1) Hardware test
2) Self-loopback test
3) Internal self-loopback test
Test results?
NG
Replace the network module
May be due to module WDT 
error
<Troubleshooting>
1) Reexamine base 
    mounting
2) Reset remote I/O module 
3) Replace remote I/O 
    module and check
<Cause>
The power is not being 
supplied.
Or, the overcurrent protection 
is active. 
<Troubleshooting>
1) Review the power supply 
    status. 
2) Check that the total 
    current consumption of 
    the modules installed on 
    the base unit does not 
   exceed the rated output 
   current of the power supply 
   module used.
<Cause>
No
No
No
D
Is the 
"ERR" LED of the 
applicable station 
lit?
OK