 26 
-
 '12 • SRK-T-125
8.  MAINTENANCE DATA
(1)  Cautions
(a)  If you are disassembling and checking an air conditioner, be sure to turn off the power before beginning. When working on 
indoor units, let the unit sit for about 1 minute after turning off the power before you begin work. When working on an outdoor 
unit, there may be an electrical charge applied to the main circuit (electrolytic condenser),  so begin work only after discharg-
ing this electrical charge (to DC 10 V or lower).
(b)  When taking out printed circuit boards, be sure to do so without exerting force on the circuit boards or package components.
(c)  When disconnecting and connecting connectors, take hold of the connector housing and do not pull on the lead wires.
(2)  Items to check before troubleshooting
(a)  Have you thoroughly investigated the details of the trouble which the customer is complaining about?
(b)  Is the air conditioner running? Is it displaying any self-diagnosis information?
(c)  Is  a power supply with the correct voltage connected?
(d)  Are the control lines connecting the indoor and outdoor units wired correctly and connected securely?
(e)  Is the outdoor unit’s service valve open?
(3)  Troubleshooting procedure (If the air conditioner does not run at all)
If the air conditioner does not run at all, diagnose the trouble using the following troubleshooting procedure. If the air condi-
tioner is running but breaks down, proceed to troubleshooting step (4).
 Important
  When all the following conditions are met, we say that the air conditioner will not run at all.
(a)  The RUN light does not light up.
(b) Theapsdonotopen.
(c)  The indoor unit fan motors do not run.
(d)  The self-diagnosis display does not function.
Troubleshooting procedure (If the air conditioner does not run at all)
Is  the  correct  voltage 
connected for the power 
supply?
With  the  power  off,  do 
theapsopenmanually,
then  close  again  when 
the power is turned on?
Is  t h e r e  a  r e c e p ti o n 
sound  emitted  from the 
unit when it is operated 
by the remote controller?
Replace the indoor PCB and 
perform an operation check.
Make sure the correct volt-
age is connected, then per-
form an operation check.
Is the current fuse on the in-
door unit PCB blown?
Proceed to the indoor PCB 
check.
Proceed to the wireless remote 
controller  troubleshooting 
procedure.
If the package components 
are not  damaged,  replace 
the fuse and perform an op-
eration check again.
*  If  the  voltage  is correct,  it  will  be 
within the following voltage range.
  198 ~ 264 V