 28 
-
 '12 • SRK-T-125
(6)  Inspection procedures corresponding to detail of trouble
Sensor error
[Broken sensor wire,
connector poor connection]
Is connector connection good?
YES
YES
NO
NO
Replace PCB.
Correct connection.
Replace sensor.
Is sensor resistance value good?
Indoor fan motor error
[Defective fan motor, connector poor 
connection, defective indoor PCB]
Is connector connection good?
YES
NO
NO
Is the output of the indoor unit 
PCB normal?
Power supply reset
NO
YES
YES
Correct connector connection
Is DC fan motor resistance value good?
Replace indoor PCB
Replace indoor fan motor
Notes (1)  See pages 30 for the DC fan motor and indoor PCB check 
procedure.
  (2)  After  making  sure  the  DC  fan  motor  and  indoor  PCB  are 
normal,  connect  the  connectors  and  confirm  that  the  fan 
motor is turning.
    (If power is turned on while one or the other is broken down, 
it could cause the other to break down also.)
* Disconnect  the  fan  motor 
connector, then  investigate 
the DC fan motor and indoor 
PCB separately.
(Short circuit)
(Broken wire)
◆
 Sensor temperature characteristics 
(Room temp.,  indoor  heat exchanger 
temp.,)
Temperature (˚C)
Resistance (k
Ω
)
Is normal state restored?
Malfunction by temporary
noise
NO
Replace fan motor (If anomaly 
persiste after replacing fan motor, 
replace indoor PCB)
YES