EasyManua.ls Logo

Modbus Slave - Rs485

Modbus Slave
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual
Modbus Slave
/
Modbus
TCP
Master
-
Document code: MN674-A003_ENG Revision 1.000 Page 10 of 30
RS485:
The connection of the RS485 in the HD674-A003-E4x-xx device must be made with a 3way
MiniFit Female connector. The pinout of Male MiniFit connector of the board is at right side of
the page.
The connection of the RS485 in the HD67-A003-E7x-xx device must be made with a AMP
SuperSeal 1.5 Male connector. The pinout of Female connector of the board is at right side of
the page.
The termination of RS485 line, with a 120Ω resistor, in the HD674-A003-Exx-xx is made
internally of the device; when the order is performed. If the device have the RS485 terminated
the code is the follow: HD674-A003-Exx-Yx; otherwise is this other: HD674-A003-Exx-Nx.
The maximum length of the cable should be 1200m (4000 feet).
Here some codes of cables:
Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil shield + braid
shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil shield + braid
shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.
Link for Mini-Fit® connectors: http://www.molex.com/molex/products/group?key=minifit_products&channel=products
Link for SuperSeal 1.5 connectors: http://www.te.com/catalog/cinf/en/c/10876/956