EasyManua.ls Logo

Modbus Slave - Translate Table

Modbus Slave
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Industrial Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual
Modbus Slave
/
Modbus
TCP
Master
-
Document code: MN674-A003_ENG Revision 1.000 Page 17 of 30
N
ORMAL
M
ODE
(
WITH
T
RANSLATE
T
ABLE
):
Using this function, the converter can be seen like a single serial Modbus slave. The address of Modbus is assigned in the “Set
Communication” section.
By pressing the Translate Tablebutton from the main window for SW674-A003 (Fig. 2), the window “Set Translate Table” appears (Fig.
4).
The data of the columns have the following meanings:
In the field “Data Type” the type of Modbus data is defined;
In the field “Address” the address of the Modbus register to which address the requests on RTU side is defined;
In the field “IP Address TCP” the IP address of the Modbus TCP slave to which the converter will address the request is defined;
In the field “Address TCP” the address of the Modbus register to which the converter will address the TCP request is defined;
In the field “NPoint” the number of consecutive registers starting from the one set is defined;
In the field “Mnemonic” a brief description is defined.
Figure 4: “Set Translate Table” window