Connecting “easy”
7
06/99 AWB 2528-1316 GB
Inputs EASY 412-DC-...
Inputs EASY 412-AC-...
+10 V
0 V
10 V
5 V
0 V
+24 V
˜
0
510
0 V
U
e
= 24 V
(20.4–28.8 V )
I
e
= 80 mA
+24 V
0 V
l7, l8
> 1 A
0 V
l1
I2
I3
I4 I5
I6
I7 I8
1 15 V
0 5 V
l = 2 mA/24 V
I7, I8 = 2.2 mA/24 V
0.5 Nm
3.5 mm
NL
0.5 Nm
3.5 mm
L
N
> 1 A
N
l1
I2
I3
I4 I5
I6
I7 I8
U
e
= 115/230 V
50/60 Hz
(97–264 V )
l
e
= 40 mA 115 V
20 mA 230 V
l1–I6 = 0.5 mA 230 V
l1–I6 = 0.25 mA 115 V
I7, I8
l = 6 mA 230 V
l = 4 mA 115 V
1 79 V
0 40 V
264 V