Engineering
3-4
01/00 AWB27-1239-GB
Figure 3-2: Plug connector assignment for the
PS416-OUT-410
For the PS416-OUT-410, the external 24-V-DC
supply voltage must be supplied to the card via at
least three cables.
For the external 24-V-DC supply voltage, use
1.5 mm
2
wire diameters. Use 0.75 mm
2
diameters for the signal cables.
The cables are passed through the bottom of the
housing.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
+24V
Q.0
+24V
Q.1
Q.2
+24V
Q.3
Q.4
Q.5
Q.6
+24V
Q.7
+24V
GND
+24V
Qx.0
+24V
Qx.1
Qx.2
+24V
Qx.3
Qx.4
Qx.5
Qx.6
+24V
Qx.7
+24V
GND
PS
416
PS
316
ZAAZAA
You can push the cables through the top if neces-
sary. In this case, the plastic blindplate on the top
of the housing must be broken and removed.