Defining the short-
circuit behaviour
The behaviour of the card in case of a short-circuit is
defined with the operating mode selector switch on
the card. This setting is only possible on the
PS416-OUT-400. The short-circuit behaviour of the
PS416-OUT-410 is equivalent to Mode 1.
Figure 3-7: Operating mode selector switch
Mode 1 (switch in position OFF/opened):
In the event of a short-circuit, all outputs of the
card are switched off until the short-circuit is
eliminated and there is a manual acknowledge-
ment with the Reset button.
A red LED indicates any short-circuit.
The cards “ZAA” output is activated. A “ZAA”
central disconnection module can be used to
register the short-circuit.