Software addressing
3-21
01/00 AWB27-1239-GB
PS416-OUT-400/-410
Operand: I
Data type: bit, byte, word, double word
1)
Line number: 1 to 9 (0 = Basic unit)
Station number: 1 to 30
(in the basic unit = 0)
Slot number: 0
Word or Byte number
(word: 0 to 34; byte: 0 to 35)
Bit number: 0 to 7
The general syntax rule is:
Operand-data type-line-rack/station-slot/module-byte/word-bit
1) A double word access is only possible with adjacent
PS416-OUT-400/-410 cards. A word access to the
PS416-OUT-410 cards is only possible if the outputs of
two adjacent PS416-OUT-410 cards are to be