Details for electromagnetic compatability (EMC) of automation devices
Emitted interference DIN EN 55 011/22 Class A
Noise immunityt
ESD DIN EN 61 000-4-2 Contact discharge
Air discharge
4 kV
8 kV
RFI DIN EN 61 000-4-3 AM/PM 10 V/m
Burst DIN EN 61 000-4-4 Line/Digital I/O
Analog I/O, Field bus
2 kV
1 kV
Surge DIN EN 61 000-4-5 Digital I/O, asymmetrical
DC line, asymmetrical
DC line, symmetrical
AC line, asymmetrical
AC line, symmetrical
0.5 kV
1 kV
0.5 kV
2 kV
1 kV
Immunity to
line-conducted
interference
DIN EN 61 000-4-6 AM 10 V