TABLE 4-2
CONTINUOUS
ALARM
CONDITION
I
PROBABLE CAUSE CORRECTIVE ACTION
I
Detector Loops Shorted
(Terminals 25 to 26)
Check if momentary Test switch
shorted
Check for defective loop wiring
Check for defective detectors
Check for defective manual pull
I
station
\
......................................
NOTE
The
AC
monitor relay (K3) and the Alarm relay (Kl) are the same and
can
be
interchanged if either
is
suspected of causing a problem.
......................................
Detector Loops Not Shorted
(Terminals 25 to 26)
TABLE 4-3
NO
BATTERY POWER
Replace Alarm relay (Kl)
b
PROBABLE CAUSE
1
CORRECTIVE ACTION
Battery Power Fuse (F3) open
Low Battery Voltage
Replace if battery power fuse
(F3)
open
Replace battery
(shoited)
Check battery wiring
Check if battery charger defective
Replace battery
a
%J
P