3.4
BATTERY
POWERED
CONDITION
Loss of primary AC power causes the Control Panel with standby batteries to
automatically go into the battery powered condition. The system's Alarm
operation is maintained. In a battery powered condition the:
o AC pilot lamp goes OFF
o Trouble condition occurs (see Paragraph 1.2.3).
Restoration of primary AC power automatically places the Control Panel in
Normal condition. The Trouble ring back feature alerts the Operator to the
changed condition.
3.5
INITIAL TEST
After the Alarm system installation is completed, wiring should be
rechecked both visually and with an ohmmeter.
Apply AC power to the system and note the AC pilot lamp on the enclosure
goes ON. Make initial voltage measurements according to Table 3-1 to
verify proper working voltages.
Figure 3-3:
C-100A-24 PCB Assembly
-
,
555
0
DOCUMENT
NO.
001-097-00
PAGE
3-4